General Specifications
Attribute
Value
Indicators
3 red/green status indicators (on CPU):
– Module status
– Network status
– POINTBus status
1 green status indicator on CPU:
– Network activity
2 green power supply status indicators on DC-DC Converter:
– System power (5V DC to POINTBus Out)
– Field power (24V DC from Field In)
Power consumption, max
10.4 W @ 28.8V DC
Power dissipation, max
5.2 W @ 28.8V DC
Thermal dissipation, max
17.75 BTU/hr @ 28.8V DC
Isolation voltage
50V (continuous), Reinforced Insulation Type, between all circuits.
Type tested at 500V AC for 60 s
Field power supply
10...28.8V DC @ 10A
Field power output
10...28.8V DC @ 9A
Module input
10...28V DC @ 1000 mA
POINTBus output, max
5V DC @ 1.0A
Dimensions (HxWxD), approx.
76.2 x 54.9 x 133.4 mm (3.0 x 2.16 x 5.25 in.)
Enclosure type rating
None (open-style)
Terminal base screw torque
0.8 Nm (7 lb-in)
Weight, approx.
255 g (0.56 lb)
Wiring category
(1)
,
(2)
1 – on power ports
1 – on communications ports
Wire Size
Power connections:
0.34... 2.1 mm
2
(22...14 AWG) solid or stranded copper wire rated
@ 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max or
90
°C (194 °F) for ControlLogix®.
Ethernet wiring:
RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e
min cable according to TIA 568-B.1 or Category 5 cable according
to ISO/IEC 24702.
North American temp code
T4A
ATEX Temp Code
T4
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication