Rockwell Automation Publication 2711P-AP006C-EN-P - November 2018
109
Optimize Runtime Performance
Chapter 9
Run the Tag Converter Wizard
Now that you have completed the pre-conversion process, you are ready to run
the tag converter wizard. The executable file is named TCW.exe.
During the conversion, most of the tags are converted to direct reference tags.
You will have to manually set scale and offset values for tags after the
conversion.
1. Double-click the TCW.exe utility.
2. Select the HMI Tag ->Direct Tag conversion type.
3. Click the ... button next to the Exported Tag Database field and load the
exported tag database.
The file is located in the directory that is specified in step
6
on page
101
.
4. Click the Add button next to Exported alarms/displays.
5. Load the exported alarms and display xml files.
The alarms file is located in the folder that is specified under step
4
on
page
108
.
TIP
The original HMI tag database is not altered.
Содержание PanelView Plus 7
Страница 1: ...Migrating PanelView Standard Applications to PanelView Plus 7 Migration Guide OriginalInstructions...
Страница 8: ...8 Rockwell Automation Publication2711P AP006C EN P November 2018 Table of Contents Notes...
Страница 64: ...64 Rockwell Automation Publication2711P AP006C EN P November 2018 Chapter 5 Review Object Mapping Notes...
Страница 118: ...118 Rockwell Automation Publication2711P AP006C EN P November 2018 Chapter 9 Optimize Runtime Performance Notes...
Страница 133: ......