Application Does Not Run
If a terminal application does not run, there may be an issue with the FactoryTalk
View Machine Edition (ME) application. Verify that a startup screen was
configured and that the runtime file is a compatible version.
If the terminal application does not run at startup, try to run the application
manually. If the application runs manually, then the operating system may be
starting up with an invalid shortcut path. Check the shortcuts in the Windows
startup folder.
\Windows\StartUp
Check the syntax of each shortcut path in the Startup folder and verify that a
valid target application exists.
Check that the application is not missing components or required DLLs. Remove
and reload the application.
Configuration Mode Access
To access Configuration mode while an application is running, your FactoryTalk
View ME application must contain a screen with a Goto Configure Mode
button. When the application is running, you can press this button to access
Configuration mode.
If a running application does not contain a Goto Configure Mode button, you
can access Configuration mode during startup by entering Safe Mode from the
general Maintenance screens. Refer to
for details.
File System Errors
File system errors are rare and can usually be corrected. The internal file system is
transaction-safe and is significantly more reliable than the FAT file system that
supports the external, removable, USB and SD storage devices. Always stop
applications before removing power so that data is cleanly flushed out to the file
system and the file system is brought to an orderly stop.
Do not remove the external USB or SD storage devices while writing to the
device is underway. Although the FactoryTalk View Machine Edition (ME)
application runs from RAM, functions such as data logging, event logging, and
historical trending, write to flash memory and should be stopped before
removing power.
TIP
If the terminal is configured to enter Configuration mode at startup and
does not, then reload the firmware.
Содержание PanelView Plus 6 1000
Страница 10: ...10 Rockwell Automation Publication 2711P UM006A EN P November 2010 Preface Notes ...
Страница 32: ...32 Rockwell Automation Publication 2711P UM006A EN P November 2010 Chapter 2 Install Terminal Notes ...
Страница 100: ...100 Rockwell Automation Publication 2711P UM006A EN P November 2010 Chapter 5 Windows CE Operating System Notes ...
Страница 154: ...154 Rockwell Automation Publication 2711P UM006A EN P November 2010 Chapter 9 Troubleshoot the System Notes ...
Страница 158: ...158 Rockwell Automation Publication 2711P UM006A EN P November 2010 Appendix A Specifications Notes ...
Страница 167: ......