Publication 1764-UM001A-US-P
Using Trim Pots and the Data Access Tool (DAT)
5-9
Error Conditions
When the DAT detects an error in its own operation, it displays the error screen.
The error screen consists of “Err” and a two-digit error code, as shown below.
The DAT can experience two different types of errors, internal errors and
communication errors.
Internal DAT Errors
Internal DAT errors are non-recoverable. When the DAT experiences an internal
error, it displays the error screen, and does not respond to any key presses. Remove
and re-install the DAT. If this does not clear the error, the DAT must be replaced.
Communication Errors
The DAT continually monitors the interface between the DAT and the controller
to ensure a good communication path. If the DAT loses communication with the
controller for more than three seconds, it generates an interface time-out error. The
DAT automatically attempts to re-establish communications. The error screen
displays until the DAT regains communications with the processor. All key presses
are ignored until the display clears.
DAT Error Codes
F1
BIT
F2
INT
ESC
ENTER
PROTECTED
Error Code
Description
Caused by
Recommended Action
00
Interface time-out
Communication traffic
Add SVC instructions to ladder program
01 to 02
Power-up test failure
Internal failure
Remove and re-insert the DAT. If failure persists,
replace the unit.
03 to 07
internal error
Internal failure
Remove and re-insert the DAT. If failure persists,
replace the unit.
08
processor owned
(1)
Another device has ownership of the controller
Release ownership by the other device
09
access denied
Cannot access that file because another device
has ownership
Release file ownership by the other device
31 to 34
internal error
Internal failure
Remove and re-insert the DAT. If failure persists,
replace the unit.
(1) This error can occur after a download in which communications configurations are changed. This error can be cleared by removing and re-installing the DAT, or by cycling
power to the controller.
Содержание micrologix 1500
Страница 1: ...MicroLogix 1500 Programmable Controllers Bulletin 1764 User Manual AB Spares...
Страница 6: ...Publication 1762 RM001A US P Preface P 4...
Страница 52: ...Publication 1764 UM001A US P 3 16 Wiring Your Controller...
Страница 78: ...Publication 1764 UM001A US P 5 10 Using Trim Pots and the Data Access Tool DAT...
Страница 96: ...Publication 1764 UM001A US P B 6 Replacement Parts...
Страница 102: ...Publication 1764 UM001A US P C 6 Troubleshooting Your System...
Страница 132: ...Publication 1764 UM001A US P F 10 System Loading and Heat Dissipation...
Страница 147: ...AB Spares...
Страница 149: ...AB Spares...