1
Publication 1764-UM001A-US-P
Chapter
5
Using Trim Pots and the Data Access Tool (DAT)
Trim Pot Operation
The processor has two trimming potentiometers (trim pots) which allow
modification of data within the controller. Adjustments to the trim pots change the
value in the corresponding Trim Pot Information (TPI) register. The data value of
each trim pot can be used throughout the control program as timer, counter, or
analog presets depending upon the requirements of the application.
The trim pots are located below the mode switch under the left access door of the
processor.
Use a small flathead screwdriver to turn the trim pots. Adjusting their value causes
data to change within a range of 0 to 250 (fully clockwise). The maximum rotation
of each trim pot is three-quarters, as shown below. Trim pot stability over time and
temperature is typically ±2 counts.
Trim pot data is updated continuously whenever the controller is powered-up.
RUN
PROG
REM
Trim Pot 0
Trim Pot 1
Maximum
(fully clockwise)
Minimum
(fully counterclockwise)
Содержание micrologix 1500
Страница 1: ...MicroLogix 1500 Programmable Controllers Bulletin 1764 User Manual AB Spares...
Страница 6: ...Publication 1762 RM001A US P Preface P 4...
Страница 52: ...Publication 1764 UM001A US P 3 16 Wiring Your Controller...
Страница 78: ...Publication 1764 UM001A US P 5 10 Using Trim Pots and the Data Access Tool DAT...
Страница 96: ...Publication 1764 UM001A US P B 6 Replacement Parts...
Страница 102: ...Publication 1764 UM001A US P C 6 Troubleshooting Your System...
Страница 132: ...Publication 1764 UM001A US P F 10 System Loading and Heat Dissipation...
Страница 147: ...AB Spares...
Страница 149: ...AB Spares...