1
Publication 1764-UM001A-US-P
Chapter
3
Wiring Your Controller
This chapter describes how to wire your controller. Topics include:
•
wiring requirements
•
using surge suppressors
•
grounding guidelines
•
sinking and sourcing circuits
•
wiring diagrams, input voltage ranges, and output voltage ranges
•
minimizing noise
Wiring Requirements
Wiring Recommendation
Wire Type
Wire Size
(1)
(1) Two wires maximum per terminal screw.
Wiring Torque
Solid
Cu-90°C (194°F)
#14 to #22 AWG
1.13 Nm (10 in-lb) rated
1.3 Nm (12 in-lb) maximum
Stranded
Cu-90°C (194°F)
#14 to #22 AWG
ATTENTION
!
Be careful when stripping wires. Wire fragments that fall into the
controller could cause damage. Once wiring is complete, be sure
the base unit is free of all metal fragments before removing
protective debris strips and installing the processor unit. Failure
to remove strips before operating can cause overheating.
ATTENTION
!
Before you install and wire any device, disconnect power to the
controller system.
Содержание micrologix 1500
Страница 1: ...MicroLogix 1500 Programmable Controllers Bulletin 1764 User Manual AB Spares...
Страница 6: ...Publication 1762 RM001A US P Preface P 4...
Страница 52: ...Publication 1764 UM001A US P 3 16 Wiring Your Controller...
Страница 78: ...Publication 1764 UM001A US P 5 10 Using Trim Pots and the Data Access Tool DAT...
Страница 96: ...Publication 1764 UM001A US P B 6 Replacement Parts...
Страница 102: ...Publication 1764 UM001A US P C 6 Troubleshooting Your System...
Страница 132: ...Publication 1764 UM001A US P F 10 System Loading and Heat Dissipation...
Страница 147: ...AB Spares...
Страница 149: ...AB Spares...