Publication 1764-UM001A-US-P
Installing Your Controller
2-7
Master Control Relay
A hard-wired master control relay (MCR) provides a reliable means for emergency
machine shutdown. Since the master control relay allows the placement of several
emergency-stop switches in different locations, its installation is important from a
safety standpoint. Overtravel limit switches or mushroom-head push buttons are
wired in series so that when any of them opens, the master control relay is
de-energized. This removes power to input and output device circuits. Refer to the
figures on pages 2-9 and 2-10.
Place the main power disconnect switch where operators and maintenance
personnel have quick and easy access to it. If you mount a disconnect switch inside
the controller enclosure, place the switch operating handle on the outside of the
enclosure, so that you can disconnect power without opening the enclosure.
Whenever any of the emergency-stop switches are opened, power to input and
output devices should be removed.
When you use the master control relay to remove power from the external I/O
circuits, power continues to be provided to the controller’s power supply so that
diagnostic indicators on the processor can still be observed.
The master control relay is not a substitute for a disconnect to the controller. It is
intended for any situation where the operator must quickly de-energize I/O devices
only. When inspecting or installing terminal connections, replacing output fuses,
or working on equipment within the enclosure, use the disconnect to shut off
power to the rest of the system.
ATTENTION
!
Never alter these circuits to defeat their function since serious
injury and/or machine damage could result.
NOTE
If you are using an external dc power supply, interrupt the dc
output side rather than the ac line side of the supply to avoid the
additional delay of power supply turn-off.
The ac line of the dc output power supply should be fused.
Connect a set of master control relays in series with the dc power
supplying the input and output circuits.
NOTE
Do not control the master control relay with the controller.
Provide the operator with the safety of a direct connection
between an emergency-stop switch and the master control relay.
Содержание micrologix 1500
Страница 1: ...MicroLogix 1500 Programmable Controllers Bulletin 1764 User Manual AB Spares...
Страница 6: ...Publication 1762 RM001A US P Preface P 4...
Страница 52: ...Publication 1764 UM001A US P 3 16 Wiring Your Controller...
Страница 78: ...Publication 1764 UM001A US P 5 10 Using Trim Pots and the Data Access Tool DAT...
Страница 96: ...Publication 1764 UM001A US P B 6 Replacement Parts...
Страница 102: ...Publication 1764 UM001A US P C 6 Troubleshooting Your System...
Страница 132: ...Publication 1764 UM001A US P F 10 System Loading and Heat Dissipation...
Страница 147: ...AB Spares...
Страница 149: ...AB Spares...