Publication 1762-UM002A-EN-P - July 2002
3-10
Module Data, Status, and Channel Configuration
Selecting Input Filter Frequency (Bits 2 through 0)
The input filter selection field allows you to select the filter frequency
for each channel and provides system status of the input filter setting
for channels 0 through 3. The filter frequency affects the following, as
explained later in this chapter:
•
noise rejection characteristics for module inputs
•
channel step response
•
channel cut-off frequency
•
effective resolution
•
module update time
Effects of Filter Frequency on Noise Rejection
The filter frequency that you choose for a module channel determines
the amount of noise rejection for the inputs. A lower frequency (50 Hz
versus 500 Hz) provides better noise rejection and increases effective
resolution, but also increases channel update time. A higher filter
frequency provides lower noise rejection, but decreases the channel
update time and effective resolution.
When selecting a filter frequency, be sure to consider cut-off
frequency and channel step response to obtain acceptable noise
rejection. Choose a filter frequency so that your fastest-changing
signal is below that of the filter’s cut-off frequency.
Table 3.2 Open-Circuit Response Definitions
Response
Option
Definition
Upscale
Sets the input data value to full upper scale value of channel data word. The
full-scale value is determined by the selected input type and data format.
Downscale
Sets the input data value to full lower scale value of channel data word. The
low scale value is determined by the selected input type and data format.
Last State
Sets the input data value to the last input value prior to the detection of the
open-circuit.
Zero
Sets the input data value to 0 to force the channel data word to 0.
Содержание MicroLogix 1200
Страница 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Страница 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Страница 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Страница 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Страница 134: ...Publication 1762 UM002A EN P July 2002 E 8 Module Configuration Using MicroLogix 1200 and RSLogix 500...
Страница 143: ...AB Parts...
Страница 144: ...Publication 1762 UM002A EN P July 2002 5 Copyright 2002 Rockwell Automation All rights reserved Printed in the U S A...