Module Data, Status, and Channel Configuration
3-7
Raw/Proportional Data
The value presented to the controller is proportional to the selected
input and scaled into the maximum data range allowed by the bit
resolution of the A/D converter and filter selected. The
raw/proportional data format also provides the best resolution of all
the data formats.
If you select the raw/proportional data format for a channel, the data
word will be a number between -32767 and +32767. For example, if a
type J thermocouple is selected, the lowest temperature of -210°C
corresponds to -32767 counts. The highest temperature of 1200°C
corresponds to +32767. See Determining Effective Resolution and
Range on page 3-14.
Engineering Units x 1
When using this data format for a thermocouple or millivolt input, the
module scales the thermocouple or millivolt input data to the actual
engineering values for the selected millivolt input or thermocouple
type. It expresses temperatures in 0.1°C or 0.1°F units. For millivolt
inputs, the module expresses voltages in 0.01 mV units.
The resolution of the engineering units x 1 data format is dependent
on the range selected and the filter selected. See Determining Effective
Resolution and Range on page 3-14.
TIP
The engineering units data formats represent real
engineering temperature units provided by the
module to the controller. The raw/proportional
counts, scaled-for-PID and percent of full-scale data
formats may yield the highest effective resolutions,
but may also require that you convert channel data
to real engineering units in your control program.
TIP
Use the engineering units x 10 setting to produce
temperature readings in whole degrees Celsius or
Fahrenheit.
Содержание MicroLogix 1200
Страница 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Страница 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Страница 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Страница 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Страница 134: ...Publication 1762 UM002A EN P July 2002 E 8 Module Configuration Using MicroLogix 1200 and RSLogix 500...
Страница 143: ...AB Parts...
Страница 144: ...Publication 1762 UM002A EN P July 2002 5 Copyright 2002 Rockwell Automation All rights reserved Printed in the U S A...