Publication 1762-UM002A-EN-P - July 2002
2-12
Installation and Wiring
To wire your module follow these steps.
1.
At each end of the cable, strip some casing to expose the
individual wires.
2.
Trim the signal wires to 2-inch (5 cm) lengths. Strip about 3/16
inch (5 mm) of insulation away to expose the end of the wire.
3.
At one end of the cable, twist the drain wire and foil shield
together, bend them away from the cable, and apply shrink
wrap. Then earth ground at the preferred location based on the
type of sensor you are using. See Grounding on page 2-8.
4.
At the other end of the cable, cut the drain wire and foil shield
back to the cable and apply shrink wrap.
5.
Connect the signal wires to the terminal block. Connect the
other end of the cable to the analog input device.
6.
Repeat steps 1 through 5 for each channel on the module.
ATTENTION
!
Be careful when stripping wires. Wire
fragments that fall into a module could cause
damage at power up.
TIP
See Appendix D
Using Thermocouple Junctions
for additional information on wiring grounded,
ungrounded, and exposed thermocouple types.
cable
signal wire
signal wire
drain wire
foil shield
signal wire
signal wire
Cut foil shield
and drain wire
Содержание MicroLogix 1200
Страница 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Страница 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Страница 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Страница 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Страница 134: ...Publication 1762 UM002A EN P July 2002 E 8 Module Configuration Using MicroLogix 1200 and RSLogix 500...
Страница 143: ...AB Parts...
Страница 144: ...Publication 1762 UM002A EN P July 2002 5 Copyright 2002 Rockwell Automation All rights reserved Printed in the U S A...