Non-recoverable – A non-recoverable fault requires the controller to be
power cycled before clearing the fault. After the controller has been power
cycled or reset, check the fault log in the Diagnostic page of the Connected
Components Workbench software, then clear the fault. The fault LED is
solid red when a non-recoverable fault occurs.
List of Error Codes for Micro800 controllers
Error Code Fault Type Description
Recommended Action
0xF000
Recoverable The controller was unexpectedly reset due to a
noisy environment or an internal hardware
failure.
If the system variable
_SYSVA_USER_DATA_LOST is set, the controller
is able to recover the user program but the user
data is cleared. If not, the Micro800 controller
program is cleared.
Perform one of the following:
•
See
Corrective Actions for Recoverable Faults on page 313
•
Check wiring to eliminate any noise, refer to
0xF001
Recoverable The controller program has been cleared. This
happened because:
•
a power-down occurred during program
download or data transfer from the memory
module
•
the cable was removed from the controller
during program download.
•
the RAM integrity test failed.
Perform one of the following:
•
See
Corrective Actions for Recoverable Faults on page 313
•
Transfer the program using the memory module restore utility.
0xF002
Non-
recoverable
The controller hardware watchdog was activated.
The controller hardware watchdog timeout
happens if program scan is more than three
seconds.
If the system variable
_SYSVA_USER_DATA_LOST is set, the controller
is able to recover the user program but the user
data is cleared. If not, the Micro800 controller
program is cleared.
Corrective Actions for Non-recoverable Faults on page 313
0xF003
Recoverable One of the following occurred:
•
The memory module hardware faulted.
•
The memory module connection faulted.
•
The memory module was incompatible with
the Micro800 controller’s firmware revision.
Perform one of the following:
•
Remove the memory module and plug it in again.
•
Obtain a new memory module.
•
See
Corrective Actions for Recoverable Faults on page 313
•
Upgrade the Micro800 controller’s firmware revision to be
compatible with the memory module. For more information on
firmware revision compatibility, go to
http://www.rockwellautomation.com/support/firmware.html
0xF004
Recoverable A failure occurred during the memory module
data transfer.
Perform one of the following:
•
See
Corrective Actions for Recoverable Faults on page 313
•
Attempt the data transfer again. If the error persists, replace the
memory module.
•
For Embedded RTC failure, restart the controller.
0xF005
Recoverable The user program failed an integrity check while
the Micro800 controller was in Run mode.
Perform one of the following:
•
See
Corrective Actions for Recoverable Faults on page 313
•
Refer to the
Wire Your Controller on page 41
.
Содержание Micro830
Страница 6: ...vi Rockwell Automation Publication 2080 UM002K EN E March 2019 Preface Notes ...
Страница 24: ...10 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 1 Hardware Overview Notes ...
Страница 70: ...56 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 4 Wire Your Controller Notes ...
Страница 88: ...74 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 5 Communication Connections Notes ...
Страница 190: ...176 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 9 Controller Security Notes ...
Страница 254: ...240 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix A Specifications Notes ...
Страница 273: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 259 Quickstarts Appendix C ...
Страница 300: ...286 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix C Quickstarts Notes ...
Страница 330: ...316 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix E Troubleshooting Notes ...
Страница 344: ...330 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix F PID Function Blocks Notes ...
Страница 352: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 338 Index Notes ...
Страница 353: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 339 ...