Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
217
Specifications
Appendix
A
Micro830 48-Point Controllers
General Specifications
Attribute
2080-LC30-48AWB
2080-LC30-48QWB
2080-LC30-48QVB
2080-LC30-48QBB
Number of I/O
48 (28 inputs, 20 outputs)
Dimensions (HxWxD)
90 x 230 x 80 mm (3.54 x 9.06 x 3.15 in.)
Shipping weight, approx.
0.725 kg (1.60 lb)
Wire size
0.2…2.5 mm
2
(24…14 AWG) solid copper wire or
0.2…2.5 mm
2
(24…14 AWG) stranded copper wire
rated @ 90 °C (194 °F) insulation max
Wiring category
(1)
2 – on signal ports
2 – on power ports
Wire type
Use copper conductors only
Terminal screw torque, max
0.6 Nm (4.4 lb-in)
(using a 2.5 mm (0.10 in.) flat-blade screwdriver)
Input circuit type
120V AC
12/24V sink/source (standard)
24V sink/source (high-speed)
Output circuit type
Relay
24V DC sink
(standard and high-speed)
24V DC source
(standard and high-speed)
Event input interrupt support
Yes, inputs 0…15 only
Power consumption, max
11 W – without plug-in modules
18.2 W – with plug-in modules
Power supply voltage range
20.4…26.4V DC Class 2
I/O rating
Input:
120V AC, 16 mA
Output:
2 A, 240V AC, general use
Input:
24V DC, 8.8 mA
Output:
2 A, 240V AC, general use
Input:
24V DC, 8.8 mA
Output:
24V DC, 1 A per point
(Surrounding air temperature 30 °C)
24 V DC, 0.3 A per point
(Surrounding air temperature 65 °C)
Insulation stripping length
7 mm (0.28 in.)
Enclosure type rating
Meets IP20
Pilot duty rating
C300, R150
—
Isolation voltage
250V (continuous),
Reinforced Insulation Type,
Outputs to Aux and
Network, Inputs to Outputs
Type tested for 60 s @
3250V DC I/O to Aux and
Network, Inputs to Outputs
250V (continuous),
Reinforced Insulation Type,
Outputs to Aux and
Network, Inputs to Outputs
Type tested for 60 s @
720V DC, Inputs to Aux and
Network, 3250V DC Outputs
to Aux and Network, Inputs
to Outputs
50V (continuous), Reinforced Insulation Type, I/O to Aux
and Network, Inputs to Outputs
Type tested for 60 s @ 720V DC, I/O to Aux and Network,
Inputs to Outputs
North American temp code
T4
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication
.
Содержание Micro830
Страница 6: ...vi Rockwell Automation Publication 2080 UM002K EN E March 2019 Preface Notes ...
Страница 24: ...10 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 1 Hardware Overview Notes ...
Страница 70: ...56 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 4 Wire Your Controller Notes ...
Страница 88: ...74 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 5 Communication Connections Notes ...
Страница 190: ...176 Rockwell Automation Publication 2080 UM002K EN E March 2019 Chapter 9 Controller Security Notes ...
Страница 254: ...240 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix A Specifications Notes ...
Страница 273: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 259 Quickstarts Appendix C ...
Страница 300: ...286 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix C Quickstarts Notes ...
Страница 330: ...316 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix E Troubleshooting Notes ...
Страница 344: ...330 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix F PID Function Blocks Notes ...
Страница 352: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 338 Index Notes ...
Страница 353: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 339 ...