Rockwell Automation Publication 2198-UM002E-EN-P - February 2018
133
Connect the Kinetix 5700 Drive System
Chapter 5
External Passive-shunt
Connections
Follow these guidelines when wiring your 2198-R
xxx
passive shunt:
• Refer to
External Passive Shunt Modules
for noise zone
considerations.
• Refer to
Passive Shunt Resistor Wiring Examples
.
• Refer to the installation instructions provided with your Bulletin 2198
shunt module, publication
.
Figure 89 - RC Connector Wiring
Table 75 - Shunt Resistor (RC) Connector Specifications
Table 76 - Shunt Resistor Compatibility
IMPORTANT
To improve system performance, run wires and cables in the wireways as
established in
.
1
2
2198-P
xxx
DC-bus Power Supply
Top View
DC-bus Power
Supply
Cat. No.
Pin
Signal
Recommended
Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
N•m (lb•in)
2198-P
xxx
RC-1
RC-2
SH
DC+
1.5…6
(16…10)
12.0 (0.47)
0.5…0.6
(4.4…5.3)
IMPORTANT
You must disconnect the internal shunt wires at the RC connector before
connecting the Bulletin 2198 shunt resistor wires.
DC-bus Power Supply
Cat. No.
Kinetix 5700 Shunt Module
(1)
Cat. No.
(1) Shunt resistor selection is based on the needs of your actual hardware configuration.
2198-R127
2198-R031
2198-R014
2198-R004
2198-P031
N/A
N/A
X
X
2198-P070
N/A
N/A
X
X
2198-P141
X
X
X
X
2198-P208
X
X
X
X