Kinetix 5700 Regenerative Bus Supply
Ground Jumper Setting for Regenerative Bus Supply
Install the Regenerative Bus Supply
These procedures assume that you have prepared your panel and understand how to bond your
system. For installation instructions regarding equipment and accessories not included here, refer
to the instructions that came with those products.
Mount the Regenerative Bus Supply
Observe these clearance requirements when mounting the regenerative bus supply:
• Additional clearance is required for cables and wires or the shared-bus connection
system connected to the top of the module.
• Additional clearance is required if other devices are installed above and/or below the
module and have clearance requirements of their own.
• Additional clearance left and right of the module is required when mounted adjacent
to noise sensitive equipment or clean wire ways.
• The recommended minimum cabinet depth is 300 mm (11.81 in.).
Ground Configuration
(1)
(1)
Refer to the Kinetix 5700 Servo Drives User Manual, publication
, for configuration diagrams.
Regenerative Bus Supply
Ground Jumper Setting
Grounded (wye)
Ground jumper installed
(default setting)
Impedance grounded
Remove ground jumper
SHOCK HAZARD:
To avoid hazard of electrical shock, perform all mounting and wiring of the
Kinetix 5700 drive system prior to applying power. Once power is applied, connector terminals can
have voltage present even when not in use.
ATTENTION:
Plan the installation of your system so that you can perform all cutting, drilling,
tapping, and welding with the system removed from the enclosure. Because the system is of the
open type construction, be careful to keep any metal debris from falling into it. Metal debris or
other foreign matter can become lodged in the circuitry and result in damage to components.