Allen-Bradley Kinetix 5700 Series Скачать руководство пользователя страница 7

Rockwell Automation Publication 2198-IN014A-EN-P - August 2018

7

Kinetix 5700 Regenerative Bus Supply

Ground Jumper Setting for Regenerative Bus Supply

Install the Regenerative Bus Supply

These procedures assume that you have prepared your panel and understand how to bond your 
system. For installation instructions regarding equipment and accessories not included here, refer 
to the instructions that came with those products.

Mount the Regenerative Bus Supply

Observe these clearance requirements when mounting the regenerative bus supply:

• Additional clearance is required for cables and wires or the shared-bus connection 

system connected to the top of the module.

• Additional clearance is required if other devices are installed above and/or below the 

module and have clearance requirements of their own.

• Additional clearance left and right of the module is required when mounted adjacent 

to noise sensitive equipment or clean wire ways.

• The recommended minimum cabinet depth is 300 mm (11.81 in.).

Ground Configuration 

(1)

(1)

Refer to the Kinetix 5700 Servo Drives User Manual, publication

 2198-UM002

, for configuration diagrams.

Regenerative Bus Supply
Ground Jumper Setting

Grounded (wye)

Ground jumper installed 
(default setting)

Impedance grounded

Remove ground jumper

SHOCK HAZARD: 

To avoid hazard of electrical shock, perform all mounting and wiring of the 

Kinetix 5700 drive system prior to applying power. Once power is applied, connector terminals can 
have voltage present even when not in use.

ATTENTION: 

Plan the installation of your system so that you can perform all cutting, drilling, 

tapping, and welding with the system removed from the enclosure. Because the system is of the 
open type construction, be careful to keep any metal debris from falling into it. Metal debris or 
other foreign matter can become lodged in the circuitry and result in damage to components.

Содержание Kinetix 5700 Series

Страница 1: ...s User Manual publication 2198 UM002 for detailed information on wiring applying power troubleshooting and integration with ControlLogix 5580 controllers with EtherNet IP communication modules or Comp...

Страница 2: ...Wiring plug connector for shunt power RC connections installed on the module These installation instructions publication 2198 IN014 Regenerative Bus Supply Cat No Module Width mm Input Voltage 1 1 Ap...

Страница 3: ...ight specifications These lifting instructions apply to catalog numbers 2198 RP200 2198 RP263 and 2198 RP312 ReadtheLiftingPrecautions Read these precautions before attempting to lift the regenerative...

Страница 4: ...secure the appropriate hardware in the designated lift points as identified in the illustrations ATTENTION To guard against equipment damage verify that the hardware is securely connected to the corre...

Страница 5: ...rt the module to the installation location IMPORTANT When approaching the full upright vertical position the weight can shift and cause the module to swing unexpectedly Control the movement of the mod...

Страница 6: ...s User Manual publication 2198 UM002 to determine the ground jumper setting ATTENTION Risk of equipment damage exists The input power ground configuration must be accurately determined When the ground...

Страница 7: ...nd right of the module is required when mounted adjacent to noise sensitive equipment or clean wire ways The recommended minimum cabinet depth is 300 mm 11 81 in Ground Configuration 1 1 Refer to the...

Страница 8: ...generative bus supply can be mounted on the far right far left or anywhere in between However the far left position is preferred to accommodate the 24V shared bus IMPORTANT Mounttheregenerativebussupp...

Страница 9: ...Hole 345 13 58 Lower Mounting Hole 420 16 54 Lower Mounting Hole 465 18 31 Lower Mounting Hole 27 5 55 0 40 0 55 0 110 55 0 110 110 165 110 110 0 00 IMPORTANT Hole spacing is measured in millimeters a...

Страница 10: ...etix 5700 drive modules Regenerative Bus Supply Cat No A mm in B mm in C mm in D mm in E 1 mm in 1 Maximum distance between lift points 2198 RP088 165 6 50 300 11 8 358 14 1 252 9 92 198 7 80 2198 RP2...

Страница 11: ...ve Bus Supply Features and Indicators on page 12 7 4 12 5 9 8 11 6 6 13 17 16 10 14 3 15 18 19 DC DC DC 24V 24V L3 L2 L1 MOD NET 2 1 1 I O 6 5 10 OK OK EN EN 5700 DC 2 1 15 20 19 20 2198 RP088 and 219...

Страница 12: ...twork status indicator 18 24V control input power CP connector 9 LCD display 19 AC Input power IPD connector 1 1 Connector plug orientation applies to 2198 RP088 and 2198 RP200 modules 2198 RP200 conn...

Страница 13: ...n 2198 UM002 for wiring examples Control Input Power CP Connector Pinout RC Pin Description Signal 2 Active shunt connections DC 1 DC CED Pin Description Signal OK Relay driven contact that provides a...

Страница 14: ...plied 24V supply COM 3 24V current sinking fast input 2 IN2 4 I O common for customer supplied 24V supply COM 5 Chassis ground SHLD 6 24V current sinking fast input 3 IN3 7 I O common for customer sup...

Страница 15: ...7 0 0 28 0 22 0 25 1 9 2 2 DC Bus power Bus bar DC DC N A 1 1 SharedDC bus powerconnectionsarealwaysmadefromdrivetodriveoverthebus barconnectionsystem Theseterminalsdonot receivediscrete wires N A 1 N...

Страница 16: ...dle high current inrush as well as fuses Make sure that the selected components are properly coordinated and meet acceptable codes which includes requirements for branch circuit protection Evaluation...

Страница 17: ...rives User Manual publication 2198 UM002 Bussmann Fuses Cat No Mersen Fuses Cat No Miniature CB Cat No Motor Protection CB Self Protected CMC Cat No Molded Case CB Cat No 2198 RP088 324 506V AC rms LP...

Страница 18: ...t protection must be provided in accordance with the National Electric Code NEC and any additional local codes Leakage current Kinetix 5700 drives produce leakage current in the protective earthing co...

Страница 19: ...IP networking and component servo drive families Kinetix Motion Accessories Specifications Technical Data publication KNX TD004 Provides product specifications for Bulletin 2090 motor and interface ca...

Страница 20: ...elp us serve your documentation needs better If you have any suggestions on how to improve this document complete the HowAre We Doing form at http literature rockwellautomation com idc groups literatu...

Отзывы: