Rockwell Automation Publication 2198-IN014A-EN-P - August 2018

Kinetix 5700 Regenerative Bus Supply

Ground Jumper Settings

The regenerative bus supply includes a ground jumper that is installed at the factory. Keep the 
ground jumper installed when input power has a grounded-wye configuration. Remove the 
ground jumper when using impedance-grounded power configurations. Refer to the 
Kinetix 5700 Servo Drives User Manual, publication

 2198-UM002

, for configuration diagrams.

The ground-jumper access door is located on the front of the regenerative bus supply. To access 
the ground jumper, insert a small screw driver or probe into the door release slot and push the 
door up behind the cover.

Remove the Ground Jumper

IMPORTANT

If you have grounded-wye power distribution in your facility, do not remove the ground 
jumper from the regenerative bus supply. For all other power distribution configurations, 
refer to the Kinetix 5700 Servo Drives User Manual, publication

 2198-UM002

, to determine 

the ground jumper setting.

ATTENTION: 

Risk of equipment damage exists. The input-power ground configuration must be 

accurately determined. When the ground jumper is installed with impedance-grounded power 
distribution or when the ground jumper is not installed with grounded-wye power distribution, 
damage to equipment can result.

ATTENTION: 

Risk of equipment damage exists. If you are using the 2198-RP

xxx

 regenerative bus 

supply, always remove the ground jumper in 2198-D

xxx

-ERS

x

 and 2198-S

xxx

-ERS

x

 inverters.

ATTENTION: 

To avoid personal injury, the ground jumper access door must be kept closed when 

power is applied. If power was present and then removed, wait at least 5 minutes for the DC-bus 
voltage to dissipate, and verify that no DC-bus voltage exists before accessing the ground jumper.

Ground Jumper Access Door
(behind cover)

Ground Jumper

Ground jumper installed

for grounded WYE power configuration

(jumper installed is default setting).

Remove jumper for impedance-grounded 

power configurations.

TIP

Hold the jumper with 

needle-nosed pliers and 

loosen captive screws.

Door Release Slot

Содержание Kinetix 5700 Series

Страница 1: ...s User Manual publication 2198 UM002 for detailed information on wiring applying power troubleshooting and integration with ControlLogix 5580 controllers with EtherNet IP communication modules or Comp...

Страница 2: ...Wiring plug connector for shunt power RC connections installed on the module These installation instructions publication 2198 IN014 Regenerative Bus Supply Cat No Module Width mm Input Voltage 1 1 Ap...

Страница 3: ...ight specifications These lifting instructions apply to catalog numbers 2198 RP200 2198 RP263 and 2198 RP312 ReadtheLiftingPrecautions Read these precautions before attempting to lift the regenerative...

Страница 4: ...secure the appropriate hardware in the designated lift points as identified in the illustrations ATTENTION To guard against equipment damage verify that the hardware is securely connected to the corre...

Страница 5: ...rt the module to the installation location IMPORTANT When approaching the full upright vertical position the weight can shift and cause the module to swing unexpectedly Control the movement of the mod...

Страница 6: ...s User Manual publication 2198 UM002 to determine the ground jumper setting ATTENTION Risk of equipment damage exists The input power ground configuration must be accurately determined When the ground...

Страница 7: ...nd right of the module is required when mounted adjacent to noise sensitive equipment or clean wire ways The recommended minimum cabinet depth is 300 mm 11 81 in Ground Configuration 1 1 Refer to the...

Страница 8: ...generative bus supply can be mounted on the far right far left or anywhere in between However the far left position is preferred to accommodate the 24V shared bus IMPORTANT Mounttheregenerativebussupp...

Страница 9: ...Hole 345 13 58 Lower Mounting Hole 420 16 54 Lower Mounting Hole 465 18 31 Lower Mounting Hole 27 5 55 0 40 0 55 0 110 55 0 110 110 165 110 110 0 00 IMPORTANT Hole spacing is measured in millimeters a...

Страница 10: ...etix 5700 drive modules Regenerative Bus Supply Cat No A mm in B mm in C mm in D mm in E 1 mm in 1 Maximum distance between lift points 2198 RP088 165 6 50 300 11 8 358 14 1 252 9 92 198 7 80 2198 RP2...

Страница 11: ...ve Bus Supply Features and Indicators on page 12 7 4 12 5 9 8 11 6 6 13 17 16 10 14 3 15 18 19 DC DC DC 24V 24V L3 L2 L1 MOD NET 2 1 1 I O 6 5 10 OK OK EN EN 5700 DC 2 1 15 20 19 20 2198 RP088 and 219...

Страница 12: ...twork status indicator 18 24V control input power CP connector 9 LCD display 19 AC Input power IPD connector 1 1 Connector plug orientation applies to 2198 RP088 and 2198 RP200 modules 2198 RP200 conn...

Страница 13: ...n 2198 UM002 for wiring examples Control Input Power CP Connector Pinout RC Pin Description Signal 2 Active shunt connections DC 1 DC CED Pin Description Signal OK Relay driven contact that provides a...

Страница 14: ...plied 24V supply COM 3 24V current sinking fast input 2 IN2 4 I O common for customer supplied 24V supply COM 5 Chassis ground SHLD 6 24V current sinking fast input 3 IN3 7 I O common for customer sup...

Страница 15: ...7 0 0 28 0 22 0 25 1 9 2 2 DC Bus power Bus bar DC DC N A 1 1 SharedDC bus powerconnectionsarealwaysmadefromdrivetodriveoverthebus barconnectionsystem Theseterminalsdonot receivediscrete wires N A 1 N...

Страница 16: ...dle high current inrush as well as fuses Make sure that the selected components are properly coordinated and meet acceptable codes which includes requirements for branch circuit protection Evaluation...

Страница 17: ...rives User Manual publication 2198 UM002 Bussmann Fuses Cat No Mersen Fuses Cat No Miniature CB Cat No Motor Protection CB Self Protected CMC Cat No Molded Case CB Cat No 2198 RP088 324 506V AC rms LP...

Страница 18: ...t protection must be provided in accordance with the National Electric Code NEC and any additional local codes Leakage current Kinetix 5700 drives produce leakage current in the protective earthing co...

Страница 19: ...IP networking and component servo drive families Kinetix Motion Accessories Specifications Technical Data publication KNX TD004 Provides product specifications for Bulletin 2090 motor and interface ca...

Страница 20: ...elp us serve your documentation needs better If you have any suggestions on how to improve this document complete the HowAre We Doing form at http literature rockwellautomation com idc groups literatu...

Отзывы: