Rockwell Automation Publication 2097-UM002D-EN-P - April 2017
63
Connect the Kinetix 350 Drive System
Chapter 4
Wire the Input Power (IPD) Connector
Table 26 - Input Power (IPD) Connector
L3
L2
L1
PE
L3
L2
L1
L2/N
L1
N
PE
L2/N
L1
N
L2
L1
PE
L2
L1
Kinetix 350
Drive
Drive Cat. No.
Terminals
Recommended
Wire Size
mm² (AWG)
Strip Length
mm (in.)
Torque Value
N•m (lb•in)
2097-V31PR0-LM
2097-V32PR0-LM
2097-V32PR2-LM
2097-V33PR1-LM
2097-V33PR3-LM
2097-V34PR3-LM
2097-V34PR5-LM
2097-V34PR6-LM
L3
L2
L1
PE
(1)
L2/N
L1
N
PE
(2)
L2
L1
PE
(3)
2.5 (14)
7 (0.28)
0.5 (4.5)
2097-V32PR4-LM
2097-V33PR5-LM
4.0 (12)
7 (0.28)
0.5 (4.5)
2097-V31PR2-LM
2097-V33PR6-LM
6.0 (10)
7 (0.28)
0.56…0.79
(5.0…7.0)
(1) Applies to 2097-V33PR
x
-LM, and 2097-V34PR
x
-LM drive modules.
(2) Applies to 2097-V31PR
x
-LM drive modules.
(3) Applies to 2097-V32PR
x
-LM drive modules.
Содержание Kinetix 350
Страница 4: ...4 Rockwell Automation Publication 2097 UM002D EN P April2017 Summary of Changes Notes ...
Страница 50: ...50 Rockwell Automation Publication 2097 UM002D EN P April2017 Chapter 3 Kinetix 350 Drive Connector Data Notes ...
Страница 154: ...154 Rockwell Automation Publication 2097 UM002D EN P April2017 Appendix C Leakage Current Specifications Notes ...
Страница 159: ...Rockwell Automation Publication 2097 UM002D EN P April2017 159 Index Notes ...
Страница 160: ...160 Rockwell Automation Publication 2097 UM002D EN P April2017 Index ...
Страница 161: ......