Rockwell Automation Publication 2097-UM001D-EN-P - November 2012
149
Configure and Start Up the Kinetix 300 Drive
Chapter 6
Table 64 - Analog Velocity
Table 65 - Analog Current
ID
Parameter Name
Description
Value
266
Drive Mode
Set to Analog Velocity
4
36
VelocityScale
Analog input velocity reference scale:
Velocity = Vinput x VelocityScale
Range: -10000…10000 rpm/V
76
AccelLimit
Accel value for Velocity mode
Range: 0.1…5,000,000 UU/s
77
DecelLimit
Decel value for Velocity mode
Range: 0.1…5,000,000 UU/s
75
EnableVelAccDec
Enable Accel/Decel function for Velocity mode
0 = Disable
1 = Enable
89
AnalogInput1Deadband
Analog input dead-band. Applied when used as a
velocity reference.
Range: 0…100 mV
90
AnalogInput1Offset
Analog input offset. Applied when used as current/
velocity reference.
Range: -10.000…10.000
85
AnalogOutFunction
Analog output function
0 = Not assigned
1 = Phase current (rms)
2 = Phase current (peak value)
3 = Motor velocity
4 = Phase current R
5 = Phase current S
6 = Phase current T
7 = Iq current
8 = Id current
86
AnalogOutVelocityScale
Analog output scale for velocity quantities
Range: 0…10 mV/rpm
29
EnableSwitchType
Enable switch function
0 = Inhibit only
1 = Enable as soon as asserted
ID
Parameter Name
Description
Value
266
Drive Mode
Set to Analog Current
5
35
CurrentScale
Current scale
Range: -
X
…+
X
Amps/Volt
X
= drive peak output current/10
89
AnalogInput1Deadband
Analog input dead-band. Applied when used as a
velocity reference.
Range: 0…100 mV
90
AnalogInput1Offset
Analog input offset. Applied when used as current/
velocity reference.
Range: -10,000…10,000
85
AnalogOutFunction
Analog output function
0 = Not assigned
1 = Phase current (rms)
2 = Phase current (peak value)
3 = Motor velocity
4 = Phase current R
5 = Phase current S
6 = Phase current T
7 = Iq current
8 = Id current
87
AnalogOutCurrentScale
Analog output scale for current related quantities.
Range: 0…10V/A
29
EnableSwitchType
Enable switch function
0 = Inhibit only
1 = Enable as soon as asserted
Содержание Kinetix 300
Страница 4: ...4 Rockwell Automation Publication 2097 UM001D EN P November 2012 Summary of Changes Notes...
Страница 18: ...18 Rockwell Automation Publication 2097 UM001D EN P November 2012 Chapter 1 Start Notes...
Страница 188: ...188 Rockwell Automation Publication 2097 UM001D EN P November 2012 Appendix A Interconnect Diagrams Notes...
Страница 216: ...216 Rockwell Automation Publication 2097 UM001D EN P November 2012 Appendix D MicroLogix Explicit Messaging Notes...
Страница 229: ...Kinetix 300 EtherNet IP Indexing Servo Drives User Manual...
Страница 230: ......