Configure and Start Up the Kinetix 300 Drive
Chapter 6
Tools for Changing Parameters
Some parameters are accessible through RSLogix 5000 software. The alternative
is to use Explicit Messaging from the Ethernet module.
Follow these steps to change parameters by using Explicit Messaging.
1.
Create a Set Attribute Single MSG instruction in the ladder logic program.
2.
Use a Class value of 374 (Hex).
3.
Use the ID of the parameter as listed in
4.
Use the Attribute value to reflect the format of the value and the
nonvolatile status of the value.
Attribute
Format
Memory Stored In
0
32-bit integer
Volatile
1
32-bit integer
Nonvolatile
2
32-bit floating point
Volatile
3
32-bit floating point
Nonvolatile
4
String
Volatile
5
String
Nonvolatile