Publication 1794-IN114A-EN-P - July 2008

Installation Instructions

FLEX I/O PROFIBUS Communications 
Adapter

1794-APBDPV1 

   

European Hazardous Location Approval

The following modules are European Zone 2 approved: 1794-APBDPV1    

Important User Information

Solid state equipment has operational characteristics differing from those of 
electromechanical equipment. Safety Guidelines for the Application, Installation and 
Maintenance of Solid State Controls (Publication 

SGI-1.1

 available from your local Rockwell 

Automation sales office or online at 

http://www.literature.rockwellautomation.com

) describes 

some important differences between solid state equipment and hard-wired electromechanical 
devices. Because of this difference, and also because of the wide variety of uses for solid 
state equipment, all persons responsible for applying this equipment must satisfy themselves 
that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or 
consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. 
Because of the many variables and requirements associated with any particular installation, 
Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the 
examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of 
information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of 
Rockwell Automation, Inc., is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.

WARNING

Identifies information about practices or circumstances that can cause an 
explosion in a hazardous environment, which may lead to personal injury or 
death, property damage, or economic loss.

IMPORTANT

Identifies information that is critical for successful application and understanding 
of the product.

ATTENTION

Identifies information about practices or circumstances that can lead to 
personal injury or death, property damage, or economic loss. Attentions 
help you:

identify a hazard

avoid a hazard

recognize the consequence

ATTENTION

Environment and Enclosure

This equipment is intended for use in a Pollution Degree 2 industrial 
environment, in overvoltage Category II applications (as defined in IEC 
publication 60664-1), at altitudes up to 2000 meters (6562 ft) without 
derating.

 

This equipment is considered Group 1, Class A industrial equipment 
according to IEC/CISPR Publication 11. Without appropriate precautions, 
there may be potential difficulties ensuring electromagnetic compatibility 
in other environments due to conducted as well as radiated disturbance.

 

This equipment is supplied as open-type equipment. It must be mounted 
within an enclosure that is suitably designed for those specific 
environmental conditions that will be present and appropriately designed 
to prevent personal injury resulting from accessibility to live parts. The 
enclosure must have suitable flame-retardant properties to prevent or 
minimize the spread of flame, complying with a flame spread rating of 
5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the 
enclosure must be accessible only by the use of a tool. Subsequent 
sections of this publication may contain additional information regarding 
specific enclosure type ratings that are required to comply with certain 
product safety certifications.

 

In addition to this publication, see:

Industrial Automation Wiring and Grounding Guidelines, for 

additional installation requirements, Allen-Bradley publication 

1770-4.1

.

NEMA Standards publication 250 and IEC publication 60529, as 

applicable, for explanations of the degrees of protection provided by 
different types of enclosure.

ATTENTION

FLEX I/O is grounded through the DIN rail to chassis ground. Use zinc 
plated yellow-chromate steel DIN rail to assure proper grounding. The use 
of other DIN rail materials (for example, aluminum or plastic) that can 
corrode, oxidize, or are poor conductors, can result in improper or 
intermittent grounding. Secure DIN rail to mounting surface approximately 
every 200 mm (7.8 in.) and use end-anchors appropriately.

ATTENTION

Preventing Electrostatic Discharge

This equipment is sensitive to electrostatic discharge, which can cause 
internal damage and affect normal operation. Follow these guidelines 
when you handle this equipment:

Touch a grounded object to discharge potential static.

Wear an approved grounding wriststrap.

Do not touch connectors or pins on component boards.

Do not touch circuit components inside the equipment.

If available, use a static-safe workstation.

Store the equipment in appropriate static-safe packaging when not 
in use.

European Zone 2 Certification (The following applies when the product bears the 
Ex or EEx Marking)

This equipment is intended for use in potentially explosive atmospheres as defined by 
European Union Directive 94/9/EC and has been found to comply with the Essential Health 
and Safety Requirements relating to the design and construction of Category 3 equipment 
intended for use in potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by 
compliance with EN 60079-15.

IMPORTANT

Observe the following additional Zone 2 certification requirements:

This equipment is not resistant to sunlight or other sources of UV 

radiation.

This equipment must be installed in an enclosure providing at least 

IP54 protection when applied in Class I, Zone 2 environments.

This equipment shall be used within its specified ratings defined by 

Allen-Bradley.

Provision shall be made to prevent the rated voltage from being 

exceeded by transient disturbances of more than 40% when applied in 
Class I, Zone 2 environments.

Secure any external connections that mate to this equipment by using 

screws, sliding latches, threaded connectors, or other means provided 
with this product.

Do not disconnect equipment unless power has been removed or the 

area is known to be nonhazardous.

Содержание FLEX I/O PROFIBUS 1794-APBDPV1

Страница 1: ... will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The enclosure must have suitable flame retardant properties to prevent or minimize the spread of flame complying with a flame spread rating of 5VA V2 V1 V0 or equivalent if non metallic The interior of the enclosure must be accessible only by the use of a tool Subsequent sections of th...

Страница 2: ...e pour les environnements dangereux Lorsque plusieurs produits sont combinés dans un système le code de température le plus défavorable code de température le plus faible peut être utilisé pour déterminer le code de température global du système Les combinaisons d équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l installation WARNING EXPLOSI...

Страница 3: ... connector according to the following pin assignments 2 Connect the cable shield to pin 1 The shield is connected to earth ground 3 Connect the data signal pins on both ends signal pin 3 and signal pin 8 4 Insert the wired connector into the mating connector on the adapter 5 Connect V DC power to the left side of the lower connector terminal E 6 Connect V common to the left side of the upper conne...

Страница 4: ...available online at www ab com networks gsd Indicators ATTENTION When connecting wiring torque terminal screws D E F and G to 0 8 Nm 7 lb in ATTENTION Do not wire more than 2 conductors on any single terminal 9 9 44560 Thumbwheel switches for setting the node address Status Indicators Indication Status Off No power Solid green Normal operation Flashing red OFF Recoverable fault FLEX K O module def...

Страница 5: ...60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 0 55 C 32 131 F Storage temperature IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 6...

Отзывы: