Publication 1794-6.5.11 - November 1997
How to Install Your Frequency Input Module
2
-3
Methods of wiring the terminal base units are shown in the illustration
below.
Wiring the Terminal Base Units (1794-TB3G shown)
!
ATTENTION: Do not daisy chain power or ground from
the terminal base unit to any ac or dc digital module terminal
base unit.
Wiring when total current draw is less than 10A
Wiring when total current draw is greater than 10A
Daisy-chaining
Individual
Total current draw through any base unit must not be greater than 10A
Combination
24V dc
24V dc
24V dc
24V dc
24V dc
24V dc
Note:
Use this configuration if using any
"noisy" dc digital I/O modules in your system.
Frequency Input Module wiring separate from digital wiring.
Note:
All modules powered by the same power supply
must be frequency or TC/RTD/mV modules for this configuration.
Note:
All modules must be frequency or TC/RTD/mV modules for this configuration.
Frequency Input
Module
Digital Input
Module
Frequency Input
Module
Frequency Input
Module
Digital Output
Module
Digital Input
Module
Frequency Input
Module
TC/RTD/mV
Module
Frequency Input
Module
Frequency Input
Module
TC/RTD/mV
Module
Frequency Input
Module
Содержание FLEX I/O 1794-IJ2
Страница 1: ...User Manual FLEX I O Frequency Input Module Cat No 1794 IJ2 Allen Bradley Allen Bradley Replacements ...
Страница 6: ...Publication 1794 6 5 11 November 1997 4 Using This Manual ...
Страница 19: ...Publication 1794 6 5 11 November 1997 1 10 Overview of the Frequency Input Module Allen Bradley Replacements ...
Страница 38: ...Publication 1794 6 5 11 November 1997 3 6 Programming Your Frequency Input Module ...
Страница 67: ...Publication 1794 6 5 11 November 1997 6 4 Troubleshoot the Frequency Input Module Allen Bradley Replacements ...