1–5
Overview of the Incremental Encoder Module
Publication 1794-6.5.15 – December 1998
Up/Down Counting Controlled by B Input
Pulse Counting (Mode 000)
1
2
3
2
1
The positive edge of the pulses are counted at input A. If input B = 0,
the counter counts up; if B = 1, the counter counts down.
Input A
Input B
0
Counter Mode = 0
Counter Register
Logic
A
B = 0/1
Counter Value
Counting Up
Counting Down
Up/Down
Up/Down counting controlled by input B
Up/Down Counting using Pulses at Inputs A and B
1
0
2
1
The counter counts up on the positive edge of the pulses at input A,
and counts down on the positive edge of input B.
Input A
Input B
0
Counter Mode = 4
Counter Register
Logic
A
B
Counter Value
Up/Down
1
Up/Down Counting using pulses at the inputs of A and B
Pulse Counting Mode (100)
Содержание FLEX I/O 1794-ID2