FLEX Ex Thermocouple/RTD Input Module
17
Publication
1797-IN004G-EN-P - August 2017
Sensor Mode Select - Write Word 1
RTD Offset Select - Write Word 2
Bit
05
04
Sensor mode for channels 0…3
13
12
Sensor mode for channels 4…7
Thermocouple Mode
0
0
External compensation
- uses cold junction sensor
0
1
Internal compensation - Uses the value selected for
reference junction
1
0
No compensation (Data is referenced to 0 °C)
1
1
Differential measurement between 2 channels
RTD Mode
0
0
2-wire RTD - no compensation
0
1
2-wire RTD with user compensation
1
0
3-wire RTD
1
1
4-wire RTD
Bit
01
00
RTD Offset Select Bits - Channel 0
03
02
RTD Offset Select Bits - Channel 1
05
04
RTD Offset Select Bits - Channel 2
07
06
RTD Offset Select Bits - Channel 3
09
08
RTD Offset Select Bits - Channel 4
11
10
RTD Offset Select Bits - Channel 5
13
12
RTD Offset Select Bits - Channel 6
15
14
RTD Offset Select Bits - Channel 7
0
0
Use channel loop compensation value stored during
calibration procedure for 2-wire RTD (default = 0
Ω)
0
1
5
Ω
1
0
10
Ω
1
1
15
Ω
Note: This parameter not applicable for Cu 10
Ω
, which defaults to 0
Ω
.