Publication 1756-UM001G-EN-P - January 2007
86
Configure PhaseManager
How Equipment Changes States
The state model’s arrows show the states through which your
equipment progresses.
•
Each arrow is called a transition.
•
A state model lets the equipment make only certain transitions.
This restriction standardizes the equipment’s behavior so that
other equipment using the same model will behave the same
way.
PhaseManager Transition Commands
Type of Transition
Description
Command
A command tells the equipment to do something. For example, the operator pushes the start button to
begin production and the stop button to halt production.
PhaseManager uses these commands:
Reset
Stop
Restart
Start
Hold
Abort
Done
Equipment goes to a waiting state when it is finished with what it is doing. You do not give the
equipment a command. Instead, you set up your code to signal when the equipment is finished.
Fault
A fault tells you that something out of the ordinary has happened. You set up your code to look for
faults and take action if it finds any. If you want to shut down your equipment as quickly as possible
when it detects a fault, set up your code to look for that fault and give the abort command if it finds it.
Holding
Hold
Idle
Start
Running
Hold
Held
Restarting
Restart
Stop
Stopping
Abort
Aborting
Stopped
Aborted
Abort
Resetting
Complete
Reset
Reset
= Transition
Command
Done — No command. Use PSC instruction instead.
Fault (specific use of the abort
command)
Your equipment can go from any state in
the box to the stopping or aborting state.
Содержание controllogix 1756-L55M12
Страница 4: ...Publication 1756 UM001G EN P January 2007 Summary of Changes 4 Notes...
Страница 10: ...Publication 1756 UM001G EN P January 2007 10 Notes...
Страница 20: ...Publication 1756 UM001G EN P January 2007 20 Directly Connect to the Controller via the Serial Port Notes...
Страница 66: ...Publication 1756 UM001G EN P January 2007 66 Place Configure and Monitor I O Modules Notes...
Страница 82: ...Publication 1756 UM001G EN P January 2007 82 Develop Applications Notes...
Страница 122: ...Publication 1756 UM001G EN P January 2007 122 Maintain Nonvolatile Memory Notes...
Страница 130: ...Publication 1756 UM001G EN P January 2007 130 Maintain the Battery Notes...
Страница 134: ...Publication 1756 UM001G EN P January 2007 134 LED Indicators Notes...