Publication 1756-UM001G-EN-P - January 2007
48
Manage Controller Communication
Produce and Consume
(Interlock) Data
The controller supports the ability to produce (broadcast) and
consume (receive) system-shared tags over ControlNet or EtherNet/IP
networks. Produced and consumed tags each require connections.
Over a ControlNet network, produced and consumed tags are
scheduled connections.
Tag Types
For two controllers to share produced or consumed tags, both must
be attached to the same network. You cannot bridge produced and
consumed tags over two networks.
The number of available connections limits the number of tags that
can be produced or consumed. If the controller uses all of its
connections for I/O and communication devices, no connections are
left for produced and consumed tags.
Available Connections
Additional Resources
For additional information, consult these publications:
•
Logix5000 Controllers Common Procedures Programming
Manual, publication 1756-PM001
•
Logix5000 Controllers Design Considerations Reference Manual,
publication 1756-RM094
Tag Type
Description
Produced
A produced tag lets other controllers to consume the tag, which means that a
controller can receive the tag data from another controller. The producing controller
uses one connection for the produced tag and one connection for each consumer. The
controller’s communication device uses one connection for each consumer.
As you increase the number of controllers that can consume a produced tag, you also
reduce the number of connections the controller and communication device have
available for other operations, such as communication and I/O.
Consumed
Each consumed tag requires one connection for the controller that is consuming the
tag. The controller’s communication device uses one connection for each consumer.
Device
Supported Connections
ControlLogix controller
250
•
1756-ENBT module
•
1756-EWEB module
128
•
1756-CNB module
•
1756-CNBR module
64
48 is the recommended maximum.
Содержание controllogix 1756-L55M12
Страница 4: ...Publication 1756 UM001G EN P January 2007 Summary of Changes 4 Notes...
Страница 10: ...Publication 1756 UM001G EN P January 2007 10 Notes...
Страница 20: ...Publication 1756 UM001G EN P January 2007 20 Directly Connect to the Controller via the Serial Port Notes...
Страница 66: ...Publication 1756 UM001G EN P January 2007 66 Place Configure and Monitor I O Modules Notes...
Страница 82: ...Publication 1756 UM001G EN P January 2007 82 Develop Applications Notes...
Страница 122: ...Publication 1756 UM001G EN P January 2007 122 Maintain Nonvolatile Memory Notes...
Страница 130: ...Publication 1756 UM001G EN P January 2007 130 Maintain the Battery Notes...
Страница 134: ...Publication 1756 UM001G EN P January 2007 134 LED Indicators Notes...