Publication 1756-UM050A-EN-P - December 2001
6-4
Using Analog I/O with Direct Connection
Add the Remote Analog I/O Module to the I/O Configuration
You must now add the new remote analog I/O module to the I/O
Configuration. In this example, you add the 1756-OF8 analog output
module and configure one of its channels for a 0V to 10V output
range. Use these steps as a guide when you are configuring different
I/O modules for your system.
1.
Right click on the
Remote_ENB
module under the I/O
Configuration folder and select
New Module
from the pop-up
window.
The
Select Module Type
window will open.
2.
Select the
1756-OF8
analog output module and click on
OK
.
TIP
For additional information on configuring a
ControlLogix analog I/O module see the
ControlLogix Analog I/O Module User Manual
,
publication 1756-6.5.9.