Publication 1756-UM050A-EN-P - December 2001
4-2
Configuring the 1756-ENBT Module
Using the Rockwell
BootP Utility
The Rockwell BootP utility is a stand alone program that incorporates
the functionality of standard BootP software with a user friendly
graphical interface. It is located in the
Utils
directory on the
RSLogix 5000
installation CD. The 1794-AENT adapter must have
BootP enabled (factory default) to use the utility.
To configure your adapter using the BootP utility, perform the
following steps:
1.
Run the BootP software. In the
BOOTP Request History
panel
you will see the hardware addresses of devices issuing BootP
requests.
2.
Double-click on the hardware address of the device you want to
configure. You will see the
New Entry
pop-up window with the
device’s Ethernet Address (MAC).
3.
Enter the
IP Address
,
Subnet Mask
, and
Gateway
you want to
assign to the device, and click on
OK
.
Содержание ControlLogix 1756-ENBT
Страница 1: ...ControlLogix Ethernet Bridge Module 1756 ENBT User Manual AB Parts...
Страница 4: ......
Страница 10: ...Publication 1756 UM050A EN P December 2001 P 6 About This User Manual Notes...
Страница 20: ...Publication 1756 UM050A EN P December 2001 1 6 About the 1756 ENBT Module...
Страница 64: ...Publication 1756 UM050A EN P December 2001 5 18 Using Rack Optimized I O...
Страница 96: ...Publication 1756 UM050A EN P December 2001 7 20 Using Produced and Consumed Tags...
Страница 130: ...Publication 1756 UM050A EN P December 2001 E 2 Autonegotiation Requirements...
Страница 136: ...Publication 1756 UM050A EN P December 2001 Glossary 6 Notes...
Страница 140: ...Publication 1756 UM050A EN P December 2001 4 Index...
Страница 143: ...AB Parts...