Publication 1790-UM003A-EN-P - May 2002
2-10
Installation and Wiring
Connect the PROFIBUS DP Terminal Connector to the 1790P-T4T0
Base Block
Follow these procedures to connect the PROFIBUS DP terminal
connector to the base block.
The required PROFIBUS female 9-pin D-sub connector
is not
supplied
with the base block - you must purchase it separately.
Before you connect female 9-pin D-sub connector to the base block,
make sure it is wired correctly as shown in the following table.
WARNING
!
If you connect or disconnect the PROFIBUS cable
with power applied to this module or any device on
the network, an electrical arc can occur. This could
cause an explosion in hazardous location
installations.
Be sure that power is removed or the area is
nonhazardous before proceeding.
Table 2.3 Wiring Descriptions for 9-Pin D-Sub Connector
Pin Number
Name
Description
1
shield
Shield, Protective Ground
2
M24V
Minus 24V Output Voltage
3
RxD/TxD-P
Receive/Transmit-Data-P
4
CNTR-P
Control-p
5
DGND
Data Ground
6
VP
Voltage-Plus
7
P24V
Plus 24V Output Voltage
8
RxD/TxD-N
Receive/Transmit-Data-N
9
CNTR-N
Control-N
Содержание CompactBlock LDX 1790D-4T0
Страница 1: ...CompactBlock LDX I O Thermocouple Modules 1790D T4T0 1790D 4T0 1790P T4T0 User Manual AB Drives ...
Страница 2: ......
Страница 8: ...Publication 1790 UM003A EN P May 2002 viii ...
Страница 50: ...Publication 1790 UM003A EN P 3 20 Module Data Status and Channel Configuration for DeviceNet ...
Страница 56: ...Publication 1790 UM003A EN P 4 6 Diagnostics and Troubleshooting ...
Страница 102: ...Publication 1790 UM003A EN P G 4 ...
Страница 108: ...Publication 1790 UM003A EN P May 2002 I 6 ...
Страница 111: ...AB Drives ...