Publication 1790-UM003A-EN-P
1-2
Overview
Thermocouple/mV Inputs and Ranges
The table below defines thermocouple types and their associated
full-scale temperature ranges. The second table lists the millivolt analog
input signal ranges that each channel will support.
Table 1.1 Thermocouple Analog Input Signal Types
Thermocouple
Type
Temperature
Range
Scaling (Counts)
Resolution
*
*
Filter set for 10 Hz
Accuracy
**
(0 to 55°C)
** Module only
B
+300 to +1800°C
+3000 to +18000
0.1°C
±4.2°C
E
-270 to +1000°C
-2700 to +10000
0.1°C
±2.5°C
J
-210 to +1200°C
-2100 to +12000
0.1°C
±2.8°C
K
-270 to +1370°C
-2700 to +13700
0.1°C
±3.3°C
R
-50 to +1768°C
-500 to +17680
0.1°C
±3.6°C
S
-50 to +1768°C
-500 to +17680
0.1°C
±3.6°C
T
-270 to 400°C
-2700 to 4000
0.1 °C
±1.3°C
N
-270 to 1300°C
-2700 to 13000
0.1°C
±3.1°C
Table 1.2 mV Analog Input Signal Types
Millivolt Input
Range
Scaling
(Counts)
Resolution
*
*
Filter set for 10 Hz
Accuracy
**
(0 to 55°C)
** Module only
10
µ
V
-76.5 to +76.5 mV
-7650 to +7650
10
µ
V
306
µ
V
Содержание CompactBlock LDX 1790D-4T0
Страница 1: ...CompactBlock LDX I O Thermocouple Modules 1790D T4T0 1790D 4T0 1790P T4T0 User Manual AB Drives ...
Страница 2: ......
Страница 8: ...Publication 1790 UM003A EN P May 2002 viii ...
Страница 50: ...Publication 1790 UM003A EN P 3 20 Module Data Status and Channel Configuration for DeviceNet ...
Страница 56: ...Publication 1790 UM003A EN P 4 6 Diagnostics and Troubleshooting ...
Страница 102: ...Publication 1790 UM003A EN P G 4 ...
Страница 108: ...Publication 1790 UM003A EN P May 2002 I 6 ...
Страница 111: ...AB Drives ...