Publication 1769-UM005A-EN-P
Diagnostics and Troubleshooting
5-5
Module Error Field
The purpose of the module error field is to classify module errors into
three distinct groups, as described in the table below. The type of error
determines what kind of information exists in the extended error
information field. These types of module errors are typically reported in
the controller’s I/O status file. Refer to your controller manual for details.
Extended Error Information Field
Check the extended error information field when a non-zero value is
present in the module error field. Depending upon the value in the
module error field, the extended error information field can contain error
codes that are module-specific or common to all 1769 analog modules.
Hardware Errors
General or module-specific hardware errors are indicated by module error
code 2. See Table 5.3 Extended Error Codes on page 5-6.
Configuration Errors
If you set the fields in the configuration file to invalid or unsupported
values, the module ignores the invalid configuration, generates a
non-critical error, and keeps operating with the previous configuration.
Table 5.3 Extended Error Codes on page 5-6 lists the possible
module-specific configuration error codes defined for the module.
Table 5.2 Module Error Types
Error Type
Module Error Field
Value
Bits 11 through 09
(Bin)
Description
No Errors
000
No error is present. The extended error field holds
no additional information.
Hardware
Errors
001
General and specific hardware error codes are
specified in the extended error information field.
Configuration
Errors
010
Module-specific error codes are indicated in the
extended error field. These error codes correspond
to options that you can change directly. For example,
the input range or input filter selection.
NOTE
If no errors are present in the module error field, the
extended error information field will be set to zero.
Содержание Compact 1769-IR6
Страница 1: ...Compact I O RTD resistance Input Module Catalog Number 1769 IR6 User Manual AB PLCs ...
Страница 10: ...Publication 1769 UM005A EN P P 4 ...
Страница 40: ...Publication 1769 UM005A EN P 3 16 Installation and Wiring ...
Страница 74: ...Publication 1769 UM005A EN P 4 34 Module Data Status and Channel Configuration ...
Страница 115: ...AB PLCs ...
Страница 116: ...Publication 1769 UM005A EN P February 2001 2001 Rockwell International Corporation Printed in the U S A ...