Rockwell Automation Publication 2100-IN012G-EN-P - August 2016
127
Auxiliary Contact Adapters
Appendix B
Install External Auxiliary
Contact Adapter on G, H, J,
and K Frame Units
Follow these instructions to install an external auxiliary contact adapter in
Bulletin 2100 Series Z or later units with circuit breakers (Bulletin 140G and
140MG). The instructions are the same for single and dual units.
This auxiliary contact kit is to be used with the following auxiliary contacts:
Catalog numbers 800F-X10, 800F-X01, 800F-X20D, 800F-X11D, and
800F-X02D.
Required Tools
You need a screwdriver, a 1/4” wrench or socket, a 5/16” wrench or socket, and
a torque wrench.
Installation
Refer to
Figure 51
and use the following steps to install external auxiliary
contact adapter.
1. Make sure that all of the power has been disconnected.
2. Verify the parts list.
3. Install auxiliary contacts.
4. Attach the external auxiliary contact assembly to the mounting plate by
using one #8-32 x 0.38 inch thread-rolling screw.
5. Tighten to these vaules:
• 20 lb•in (2.2 N•m) for #6-20 screws
• 32 lb•in (3.6 N•m) for #8-32 screws
6. Check continuity to ensure proper operation of auxiliary contacts.
TIP
De-energize all of the power sources to the motor control center before
installing auxiliary contact adapter. Failure to de-energize all of the power
sources can result in severe injury or death.
Содержание CENTERLINE 2100
Страница 4: ...4 Rockwell Automation Publication 2100 IN012G EN P August 2016 Summary of Changes Notes ...
Страница 106: ...106 Rockwell Automation Publication 2100 IN012G EN P August 2016 Chapter 10 Maintenance after Fault Condition Notes ...
Страница 108: ...108 Rockwell Automation Publication 2100 IN012G EN P August 2016 Chapter 11 Renewal Parts Notes ...
Страница 134: ...134 Rockwell Automation Publication 2100 IN012G EN P August 2016 Index Notes ...
Страница 135: ......