Rockwell Automation Publication 1783-UM007I-EN-P - December 2017
Chapter 3
Configure Switch Features
In the example that is shown in
, E1 or E2 can be configured as the
primary no-neighbor port.
Figure 42 - Ring Topology Example
REP has these limitations:
•
You must configure each segment port; an incorrect configuration can
cause forwarding loops in the networks.
•
REP can manage only one failed port within the segment; multiple port
failures within the REP segment cause loss of network connectivity.
Configure REP in networks only with redundancy. Configuring REP in a
network without redundancy causes loss of connectivity.
Link Integrity
REP does not use an end-to-end polling mechanism between edge ports to
verify link integrity. It implements local link failure detection. The REP Link
Status Layer (LSL) detects its REP-aware neighbor and establishes
connectivity within the segment. All VLANs are blocked on an interface until
it detects the neighbor. After the neighbor is identified, REP determines the
neighbor port to become the alternate port and which ports forward traffic.
Each port in a segment has a unique port ID. The port ID format is similar to
the format used by the spanning tree algorithm: a port number (unique on the
bridge), associated to a MAC ID (unique in the network). When a segment
port is coming up, its LSL starts sending packets that include the segment ID
and the port ID. The port is declared as operational after it performs a three-
way handshake with a neighbor in the same segment.
273792
R
R
E
E
273792
REP Not Supported
REP Ports Configured at Transit Ports
E1
E2
Содержание armorstratix 5700
Страница 10: ...10 Rockwell Automation Publication 1783 UM007I EN P December 2017 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1783 UM007I EN P December 2017 Preface Notes ...
Страница 72: ...72 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 2 Get Started Notes ...
Страница 148: ...148 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features ...
Страница 282: ...282 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features Notes ...
Страница 317: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 317 Monitor the Switch Chapter 4 ...
Страница 319: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 319 Monitor the Switch Chapter 4 ...
Страница 325: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 325 Monitor the Switch Chapter 4 ...
Страница 338: ...338 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 5 Troubleshoot the Switch Notes ...
Страница 396: ...396 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix A DataTypes Notes ...
Страница 404: ...404 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix B Port Assignments for CIP Data Notes ...
Страница 450: ...450 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix D Cables and Connectors Notes ...
Страница 457: ......