![Allen-Bradley ArmorStart 290E Скачать руководство пользователя страница 145](http://html.mh-extra.com/html/allen-bradley/armorstart-290e/armorstart-290e_user-manual_2900167145.webp)
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
145
Bulletin 290E/291E/294E Programmable Parameters
Chapter
4
Miscellaneous Configuration Group
NetworkOverride
This parameter allows for the local logic
to override a Network fault.
0 = Disable
1 = Enable
Parameter Number
64
Access Rule
GET/SET
Data Type
BOOL
Group
Misc. Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
CommsOverride
This parameter allows for local logic to
override an I/O connection timeout.
0 = Disable
1 = Enable
Parameter Number
65
Access Rule
GET/SET
Data Type
BOOL
Group
Misc. Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
KeypadMode
This parameter selects if the keypad
operation is maintained or momentary.
0 = Momentary
1 = Maintained
Parameter Number
66
Access Rule
GET/SET
Data Type
BOOL
Group
Misc. Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
KeypadDisable
This parameter disables all keypad
function except for the “OFF” and “RESET”
buttons.
0 = KeypadEnabled
1 = KeypadDisabled
Parameter Number
67
Access Rule
GET/SET
Data Type
BOOL
Group
Misc. Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Содержание ArmorStart 290E
Страница 1: ...ArmorStart LT Distributed Motor Controller Catalog Numbers 290E 291E 294E User Manual ...
Страница 8: ...8 RockwellAutomationPublication290E UM001B EN P June2012 Summary of Changes Notes ...
Страница 66: ...66 RockwellAutomationPublication290E UM001B EN P June2012 Chapter 2 Installation and Wiring Notes ...
Страница 98: ...98 RockwellAutomationPublication290E UM001B EN P June2012 Chapter 3 Product Commissioning Notes ...
Страница 228: ...228 RockwellAutomationPublication290E UM001B EN P June2012 Appendix B CIP Information Notes ...
Страница 251: ......