Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
121
Bulletin 290E/291E/294E Programmable Parameters
Chapter
4
Advanced Configuration
OLWarningLevel
This parameter determines the Overload
Warning Level in % Thermal Capacity Used
(%TCU).
Parameter Number
69
Access Rule
GET
Data Type
USINT
Group
Advanced Config.
Units
%TCU
Minimum Value
0
Maximum Value
100
Default Value
85
JamInhibitTime
This parameter determines the time
during motor starting that Jam detection
is inhibited.
Parameter Number
70
Access Rule
GET
Data Type
USINT
Group
Advanced Config.
Units
secs.
Minimum Value
0
Maximum Value
250
Default Value
10
JamTripDelay
This parameter determines how much
time above the Jam Level before the unit
will trip.
Parameter Number
71
Access Rule
GET
Data Type
USINT
Group
Advanced Config.
Units
x.x secs
Minimum Value
1
Maximum Value
25.0
Default Value
5.0
JamTripLevel
This parameter determines the Jam Trip
Level as a percentage of Full Load Amps.
Parameter Number
72
Access Rule
GET
Data Type
UINT
Group
Advanced Config.
Units
%FLA
Minimum Value
50
Maximum Value
600
Default Value
250
Содержание ArmorStart 290E
Страница 1: ...ArmorStart LT Distributed Motor Controller Catalog Numbers 290E 291E 294E User Manual ...
Страница 8: ...8 RockwellAutomationPublication290E UM001B EN P June2012 Summary of Changes Notes ...
Страница 66: ...66 RockwellAutomationPublication290E UM001B EN P June2012 Chapter 2 Installation and Wiring Notes ...
Страница 98: ...98 RockwellAutomationPublication290E UM001B EN P June2012 Chapter 3 Product Commissioning Notes ...
Страница 228: ...228 RockwellAutomationPublication290E UM001B EN P June2012 Appendix B CIP Information Notes ...
Страница 251: ......