Rockwell Automation Publication 1732E-UM001A-EN-P - December 2019
31
Configure Module Using Generic Profile
Chapter 3
3.
Download the configuration to the controller and go online.
Process Data for the
Module
Output Data
16-bit output data, default I/O mapping, assembly Instance 100.
Input Data
16-bit input data with diagnostics, default I/O mapping, assembly Instance 101.
Output
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 0
C7
C6
C5
C4
C3
C2
C1
C0
Byte 1
C15
C14
C13
C12
C11
C10
C9
C8
Input
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 0
C7
C6
C5
C4
C3
C2
C1
C0
Byte 1
C15
C14
C13
C12
C11
C10
C9
C8
Byte 2
InternalFault
0
0
0
OutputGroupFault InputGroupFault
FieldPowerLow
PowerFault
Byte 3
Pt14_15InputSho
rtCirctui
Pt12_13InputSho
rtCircuit
Pt10_11InputSho
rtCircuit
Pt08_09InputSho
rtCircuit
Pt06_07InputSho
rtCircuit
Pt04_05InputSho
rtCircuit
Pt02_03InputSho
rtCircuit
Pt00_01InputSho
rtCircuit
Byte 4
0
0
0
0
0
0
0
0
Byte 5
Pt07OutputFault
Pt06OutputFault
Pt05OutputFault
Pt04OutputFault
Pt03OutputFault
Pt02OutputFault
Pt01OutputFault
Pt00OutputFault
Byte 6
Pt15OutputFault
Pt14OutputFault
Pt13OutputFault
Pt12OutputFault
Pt11OutputFault
Pt10OutputFault
Pt09OutputFault
Pt08OutputFault