Rockwell Automation Publication 8720MC-RM001K-EN-P - September 2018
89
Configure Parameters
Chapter 7
Factory Parameters
Factory parameters are initially set at the factory and usually do not require
adjustment or modification in the field.
F.000 Password
A password must be set to this
parameter to change the
Factory parameters.
Parameter Range
0…999
Default Setting
0
Parameter Type
Configurable
Refer also to Parameters
F.001
Unit Selection
Once a password is set, it is retained until power to the 8720MC-RPS unit is removed. Therefore, once a password is set to this parameter, the
Factory parameters can be changed at any time until power to the unit is removed.
Even though a password has been set to this parameter, the password can be cancelled by setting other value than the password to this
parameter.
Password can be set at any time while the 8720MC-RPS unit is operating or stopping, or fault occurred.
Use the following procedure to set a password:
1. Press PRG. U.--- is displayed, and the PROGRAM status indicator turns ON.
2. Press
or
until F.--- is displayed.
3. Press ENT. F.000 is displayed.
4. Press ENT. 0 is displayed.
5. Press
until 55 is displayed (hold down
to increase the scroll speed).
6. Press ENT to enter the value.
ATTENTION:
Only qualified electrical personnel familiar with the construction and operation of
this equipment and the hazards involved should change the Factory Parameters. Read and
understand this instruction manual in its entirety before proceeding. Failure to change
parameter values could result in destruction of the equipment, severe bodily injury or loss of life.
F.001 Unit Selection
As the type of the 8720MC-RPS
unit, this parameter sets a
character code representing the
input power supply voltage and
the unit capacity. For most
applications, we recommend
that this parameter not be
adjusted.
IMPORTANT:
This parameter is
available from software version
3.00 or later (to be shown on
the parameter F.018).
IMPORTANT:
The parameters
reset to factory settings if the
ENT key is pressed, even though
the unit type selection remains
intact.
Parameter Range
065.b
37 kW, 65 A unit for 460V, single 37 kW unit
130.b
75 kW, 130 A unit for 460V, 2 paralleled 37 kW units
195.b
110 kW, 195 A unit for 460V, 3 paralleled 37 kW units
190.b
125 kW, 190 A unit for 460V, single 125 kW unit
380.b
250 kW, 380 A unit for 460V, 2 paralleled 125 kW units
570.b
375 kW, 570 A unit for 460V, 3 paralleled 125 kW units
Default Setting
Unit-dependent
Parameter Type
Requiring the password, configurable only while the unit stops.
Refer also to Parameters
F.002
Rated Current
• The unit type (065: 65A, for example) is represented by the AC input current value.
• .b is the AC input power voltage value (380…460V AC).
• Setting a unit type to this parameter resets all the parameters to factory default settings, and cancels the password.
• When the password is not set, or during operation even though the password has been set, the unit capacity cannot be changed.
IMPORTANT:
065.b, 130.b, 190.b, 195.b, 380.b, and 570.b are the only valid parameter settings.
ATTENTION:
Only qualified electrical personnel familiar with the construction and operation of
this equipment and the hazards involved should change the Factory Parameters. Read and
understand this instruction manual in its entirety before proceeding. Failure to change
parameter values could result in destruction of the equipment, severe bodily injury or loss of life.