Publication 2707-UM005B-EN-P
C-6
MicroView Special Controller Functions
Reading / Writing
Controller Timer Files
To read/write the contents of controller Timer files:
1.
Press [1] P-A/D from the Special Menu to access the P-A/D
function.
You are prompted for a file type:
2.
Press [NEXT] and [PREV] keys to scroll through the file types.
Select Timer and press [
].
3.
You are prompted for an element number:
4.
Enter the element number and press [
].
You are shown the timer accumulator value
5.
Press [NEXT] to display the timer preset value:
6.
You can change the Acc and Pre values by pressing the [PREV]
or [NEXT] keys to move the cursor to the field to change, and
then entering a new value.
7.
Press the [
] key to enter new accumulator or preset values to
the displayed timer address.
8.
Press [NEXT] again to display the status bits:
9.
To exit, press the [CE] key to return to the initial P-A/D screen.
You can press the [CE] key at any time during the P-A/D
function.
10.
Press the [MENU] key at any time to exit the P-A/D function and
display the Main Menu.
ATTENTION
!
Do not send negative timer values to the
controller. Negative timer values cause a fault
in the controller.
Select File Type:
O (Output)
Elem=___________
Accumulator
Accumulated Value
File=T4
Elem=008
00120
Acc
Preset
Preset Value
File=T4
Elem=008
00200
Pre
Bits(Enable, Timer Timing, Done)
Status
File=T4
Elem=008 0
EN
TT
DN
0
0
Содержание 2707-MVH232
Страница 1: ...MicroView Operator Interface Module Catalog No 2707 MVH232 2707 MVP232 User Manual...
Страница 6: ...Publication 2707 UM005B EN P Table of Contents iv...
Страница 28: ...Publication 2707 UM005AB EN P 3 12 Initial Setup and Mode Menu...
Страница 50: ...Publication 2707 UM005B EN P July 2000 6 6 Installing the MicroView Operator Interface...
Страница 54: ...Publication 2707 UM005B EN P 7 4 Communication Connections and Setup...
Страница 70: ...Publication 2707 UM005B EN P A 2 Specifications...
Страница 74: ...Publication 2707 UM005B EN P B 4 MicroView Cable Diagrams...
Страница 91: ...B...