88
Rockwell Automation Publication 23PFC-TG001A-EN-P - March 2018
Chapter 4
Frame B Field Controller Part Replacement Procedures
Install the 115V AC to 24V DC I/O Converter Circuit Board
Install the 115V AC to 24V DC I/O converter board in reverse order of
removal.
Control Circuit Board
Replacement
Remove the Control Circuit Board
1. Read the General Safety Precautions on page
2. Save the device and adapter parameter configuration by using one of
these methods:
• HIM Set - see Save to a HIM Set on page
• Download the field controller and adapter parameters to an offline
database file by using DriveExecutive™. See the on-line help that is
provided with DriveExecutive for information on how to save
database files.
• Export a configuration file by using Connected Components
Workbench® software. See the on-line help that is provided with
Connected Components Workbench for information on how to
export a device configuration file.
3. Remove power from the device (see page
4. Remove the protective covers from the device (see page
5. Remove the communication adapter and EMI shield from the control
board (see page
6. If installed, remove the I/O expansion circuit board (see page
).
7. If installed, remove the 115V AC to 24V DC I/O converter circuit
board (see page
Содержание 23PFC
Страница 8: ...8 Rockwell Automation Publication 23PFC TG001A EN P March 2018 Preface Notes ...
Страница 130: ...130 Rockwell Automation Publication 23PFC TG001A EN P March 2018 Appendix A Schematics Notes ...
Страница 142: ...142 Rockwell Automation Publication 23PFC TG001A EN P March 2018 Appendix B Circuit Board Layouts and Connections Notes ...
Страница 148: ...148 Rockwell Automation Publication 23PFC TG001A EN P March 2018 Index Notes ...
Страница 149: ......