Rockwell Automation Publication 2080-UM005E-EN-E - March 2018
107
Using microSD Cards
Chapter 9
Data Log Directory Structure
The following table summarizes data logging performance onMicro820
controllers.
The DATALOG folder is created under the current project directory
in the microSD card. In this example, the current project directory is
MYPROJECT. By default, the current project directory name is taken
from the downloaded project’s controller name or from the
ConfigMeFirst.txt. See
ConfigMeFirst.txt Configuration Settings on
page 100
.
Subdirectories are also created following the controller RTC
timestamp. This means that if RTC date at the time of function block
execution is February 02, 2013, the subfolder 2013 is created under
DATALOG. Under the 2013 folder, the subfolder 02 (which stands for
the month of February) is created. Under 02, another subfolder 02 is
created, corresponding to the current date.
Under the current working folder, the subfolder Grp01 is created. A
maximum of 50 Grpxxx folders can be generated on the microSD
card per day.
Under the current Grpxxx working folder, the data log file File01.txt
is created. Once this file reaches more than 4 KB, another file,
File02.txt, is automatically created to store data. The file size is kept
small in order to minimize data loss in case the card is removed or
when there is unexpected power off.
Each Grpxx folder can accommodate up to 50 files. This means that,
for example, when the Grp01 folder already stores 50 files, a new
folder Grp02 is automatically created to store the next data log files
for that day. This automatic folder and file generation goes on until
the Grpxx folder reaches 50 for that day.
When a microSD card is inserted, the DLG function block looks for
the last Grpxx folder and filexx.txt file, and proceeds to do the data
logging based on that information.
These data log
files are for
February 2, 2014.
Data Log Specifications
Attribute
Value
Maximum datasets
10
All datasets are stored in the same file.
Maximum variables per dataset
128
Configured in Connected Components
Workbench software.
Minimum size per file
4 KB
Maximum files per Grpxx folder
(1)
(1) Once the data log limits is reached (that is, 50 Grpxx folders per day, then an error (ErrorID 3:
DLG_ERR_DATAFILE_ACCESS) is returned.
50
When directory is full, a new directory is
automatically created in RUN mode.
Maximum files (Filexx.txt) per day
50
When file reaches maximum size, a new file is
automatically created in RUN mode.
Typical data per day
10 MB
Содержание 2080-LC20-20AWB
Страница 6: ...vi Rockwell Automation Publication 2080 UM005E EN E March 2018 Preface Notes...
Страница 10: ...x Rockwell Automation Publication 2080 UM005E EN E March 2018 Table of Contents Notes...
Страница 16: ...6 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 1 Hardware Overview Notes...
Страница 40: ...30 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 2 About Your Controller Notes...
Страница 46: ...36 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 3 Install Your Controller Notes...
Страница 66: ...56 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 4 Wire Your Controller Notes...
Страница 106: ...96 Rockwell Automation Publication 2080 UM005E EN E March 2018 Chapter 8 Using the Micro800 Remote LCD Notes...
Страница 162: ...152 Rockwell Automation Publication 2080 UM005E EN E March 2018 Appendix B Troubleshooting Notes...
Страница 173: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 163 Quickstarts Appendix C...
Страница 210: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 200 Index Notes...
Страница 211: ...Rockwell Automation Publication 2080 UM005E EN E March 2018 201...