Rockwell Automation Publication 193-UM014C-EN-P - August 2016
45
Add Devices to the DeviceNet Network
Chapter 4
Simple
1. From the EtherNet/IP communication auxiliary module web page,
navigate to Scan List>Configuration>Scan List.
The EtherNet/IP communication auxiliary module reads the available
DeviceNet modules on the DeviceNet network.
2. Click Config. The lowest six DeviceNet node addresses populate into
the Scan List field on the right.
3. Click OK to complete the configuration.
The DeviceNet scanner on the EtherNet/IP communication auxiliary
module begins scanning the DeviceNet devices.