Publication 1794-6.5.12 - November 1997
3-4
Programming Your Thermocouple/RTD Input Module
PLC-5/250 Processor
Block transfer instructions with the PLC-5/250 processor use a control
file and a data file. The block transfer control file contains the data table
section for module location, the address of the block transfer data file and
other related data. The block transfer data file stores data that you want
transferred to the module (when programming a BTW) or from the
module (when programming
a BTR).
The programming terminal will automatically select the control file based
on rack, group and module, and whether it is a read or write. A different
block transfer control file is used for the read and write instructions
for your module. A different block transfer control file is required for
every module.
EN
BTR
BLOCK TRANSFER READ
Rack
Group
Slot
Control
02
2
1
N22:200
DN
Data File
Length
Continuous
N22:101
0
N
ER
EN
BLOCK TRANSFER WRITE
Rack
Group
Slot
Control
02
2
1
N22:205
DN
Data File
Length
Continuous
N22:1
0
N
ER
N22:200
15
N22:200
15
N22:205
15
Rung 2:0
The IRT8 module is located in rack 2, I/O group 2, slot 1. The integer control file starts at N22:200, is 5 words long and
is compatible with all PLC-5 family members. The data obtained by the PLC-5 processor from the IRT8 module is
placed in memory starting at N22:101, and with the default length of 0, is 11 words long. The length can be any number
between 0 and 11. In enhanced PLC-5 processors
, the block transfer data type may be used as a control file.
N22:205
15
Rung 2:1
The IRT8 module is located in rack 2, group 2, slot 1. The integer control file starts at N22:205, is a 5 words long and is
compatible will all PLC-5 family members. The data sent by the PLC-5 processor to the IRT8 module starts at N22:1, and
with the default length of 0, is 4 words long. Valid BTW lengths: 0, 1, 2, 3, and 4. In enhanced PLC-5 processors , the
block transfer data type may be used as a control file.
IRT8 BTR
Enable Bit
IRT8 BTW
Enable Bit
IRT8 BTR
Control File
IRT8 BTR
Enable Bit
IRT8 BTW
Enable Bit
IRT8 BTW
Control File
PLC-5 Processor
Program Example
BTW
Enhanced PLC-5 processors include: PLC-5/11, -5/20, -5/3x, -5/4x, and -5/6x.
1
1
1
Содержание 1794-IRT8
Страница 1: ...User Manual Thermocouple RTD Millivolt Input Module Cat No 1794 IRT8 Allen Bradley Allen Bradley PLCs ...
Страница 3: ...Publication 1794 6 5 12 November 1997 2 Allen Bradley PLCs ...
Страница 7: ...Publication 1794 6 5 12 November 1997 P 4 Using This Manual Allen Bradley PLCs ...
Страница 33: ...Publication 1794 6 5 12 November 1997 3 6 Programming Your Thermocouple RTD Input Module Allen Bradley PLCs ...