Rockwell Automation Publication 1788-UM057B-EN-P - September 2014
23
Set Up in the Studio 5000 Logix Designer Application
Chapter 2
4.
Set the RPI for the linking device.
5.
Click OK to add the linking device to the I/O tree.
RSNetWorx for ControlNet Configuration
See the RSNetWorx for ControlNet Getting Results Guide, publication
, for more details.
Follow these steps to configure the ControlNet network.
1.
Launch RSNetWorx™ for ControlNet and create a file.
2.
Click the Online button.
The Browse for Network window appears with the drivers you have
installed on your system.
IMPORTANT
The recommended RPI is 1/2 the macrocycle time. Calculate the macrocycle by
calculating the total response time of all field devices on the segment and then
add 100
…
200 ms for class 2 (DTM message) data. If the RPI is too low, class 1
data (PVs and status) does not update each cycle, and class 2 data responses
can be slow.