Rockwell Automation Publication 1769-UM021G-EN-P - October 2015
301
Use a Secure Digital Card
Chapter 12
If you choose On Power Up or On Corrupt Memory, you must also choose
the mode that you want the controller to go to after the load:
•
Remote Program
•
Remote Run
7.
In the Automatic Firmware Update box, use the default (disable) or choose
the firmware supervisor option.
8.
Click <- Store.
A dialog box asks for confirmation of the store.
9.
To store the project, click Yes.
10.
Click OK.
After you click Store, the project is saved to the SD card as indicated by the
controller status indicators. These conditions can exist:
•
While the
store is in progress
, the following occurs:
–
The OK indicator is flashing green.
–
The SD indicator is flashing green.
–
A dialog box indicates that the store is in progress.
•
When the
store is complete
, the following occurs:
–
The controller resets itself.
When the controller is resetting itself, the status indicators execute a
sequence of state changes, for example, a brief time with the OK status
indicator in the solid red state. Wait for the controller to complete the
sequence.
–
After the controller fully resets itself, the OK indicator is solid green.
–
The SD indicator is off.
IMPORTANT
The Firmware Supervisor option is not used to upgrade the
controller firmware.
IMPORTANT
Store is not active if a SD card is locked.
IMPORTANT
Allow the store to complete without interruption. If you interrupt the
store, data corruption or loss can occur.