Chapter 8
Use I/O Modules with CompactLogix 5370 L2 Controllers
Common Configuration Parameters
While the configuration options vary from module to module, there are some
common options you typically configure when using Compact I/O modules in a
CompactLogix 5370 L2 control system, as described in
Table 26
.
Table 26 - Common Configuration Parameters
Configuration Option
Description
Requested packet interval (RPI)
The RPI specifies the interval at which data is transmitted or received over a connection. For 1769 Compact Local I/O modules, data is
transmitted to the controller at the RPI.
When scanned on the local bus or over an EtherNet/IP network, input modules are scanned at the RPI specified in the module
configuration. Typically, you configure an RPI in milliseconds (ms). For I/O modules, the range is 0.5…750 ms.
When scanned over a DeviceNet network via a 1769-SDN scanner in the CompactLogix 5370 L2 control system, distributed input
modules are scanned at the rate the DeviceNet adapter that connects the input modules to the network supports. For example, if your
system includes a remote system of 1734 POINT I/O™ modules on a DeviceNet network, the 1769-SDN scanner can only scan the
distributed 1734 POINT I/O modules as quickly as the 1734-ADN DeviceNet adapter can transmit the data.
Module definition
Set of configuration parameters that affect data transmission between the controller and the I/O module. The parameters include the
following:
•
Series - Hardware series of the module.
•
Revision - Major and minor firmware revision levels that are used on the module.
•
Electronic Keying - See
for Electronic Keying information.
•
Connection - Type of connection between the controller writing the configuration and the I/O module, such as Output.
•
Data format - Type of data that is transferred between the controller and I/O module and what tags are generated when the
configuration is complete.
Module Fault on Controller If Connection
Fails While in Run Mode
This option determines how the controller is affected if the connection to an I/O module fails in Run mode. You can configure the project
so that a connection failure causes a major fault on the controller or not.
The default setting is for the option to be enabled, that is, if the connection to an I/O module fails in Run mode, a major fault occurs on
the controller.