Publication 1763-RM001C-EN-P - October 2009
232
File Instructions
FFU - First In, First Out
(FIFO) Unload
Instruction Type: output
On a false-to-true rung transition, the FFU instruction unloads words or
long words from a user-created file called a FIFO stack. The data is
unloaded using first-in, first-out order. After the unload completes, the
data in the stack is shifted one element toward the top of the stack and
the last element is zeroed out. Instruction parameters have been
programmed in the FFL - FFU instruction pair shown below.
This instruction uses the following operands:
•
FIFO - The FIFO operand is the starting address of the stack.
EU
DN
EM
FFU
FIFO Unload
FIFO
#N7:0
Dest
N7:1
Control
R6:0
Length
1<
Position
0<
FFU
Execution Time for the FFU Instruction
Controller
Data Size
When Rung Is:
True
False
MicroLogix 1100
word
38.87
μ
s
37.06
μ
s
long word
38.87
μ
s
37.06
μ
s
(EU)
(EM)
(DN)
FFL
FIFO LOAD
Source
N7:10
FIFO
#N7:12
Control
R6:0
Length
34
Position
9
FFU
FIFO UNLOAD
FIFO
#N7:12
Dest
N7:11
Control
R6:0
Length
34
Position
9
(EN)
(DN)
(EM)
Destination
Position
N7:11
N7:12
0
N7:13
1
FFU instruction
unloads data from
stack #N7:12 at
position 0, N7:12
N7:14
2
3
4
5
34 words are allocated
for FIFO stack starting
at N7:12, ending at
N7:45
6
7
Source
8
N7:10
9
FFL instruction loads
data into stack
#N7:12 at the next
available position, 9
in this case.
N7:45
33
Loading and Unloading of Stack #N7:12
FFL and FFU Instruction Pair