Mount the Module on a Panel
Use the dimensional template shown below to mount the module. The preferred mounting
method is to use two M4 or #8 panhead screws per module. M3.5 or #6 panhead screws may also
be used, but a washer may be needed to ensure a good ground contact. Mounting screws are
required on every module.
TIP
For environments with greater vibration and shock concerns, use the panel
mounting method described below, instead of DIN-rail mounting.
End Anchor
End Anchor
MicroLogix 1200
Controller
MicroLogix 1200
Expansion I/O
MicroLogix 1200
Expansion I/O
MicroLogix 1200
Expansion I/O
90
(3.54)
100
(3.94)
40.4
(1.59)
40.4
(1.59)
14.5
(0.57)
For more than two modules: (number of modules - 1) x 40 mm (1.58 in.)