Monitor Status and Handle Faults
Chapter 7
De-energize to Trip System
GuardLogix controllers are part of a de-energize to trip system, which means that
zero is the safe state. Some, but not all, safety module faults cause all module
inputs or outputs to be set to zero (safe state). Faults associated to a specific input
channel result in that specific channel being set to zero; for example, a pulse test
fault that is specific to channel 0 results in channel 0 input data being set to the
safe state (0). If a fault is general to the module and not to a specific channel, the
combined status bit displays the fault status and all module data is set to the safe
state (0).
For information on how to use the RSLogix 5000® software, version 14 safety
application instructions, see
of this manual and the GuardLogix
Safety Application Instructions Safety Reference Manual, publication
Get System Value (GSV) and Set System Value (SSV) Instructions
The GSV and SSV instructions let you get (GSV) and set (SSV) controller
system data stored in device objects. When you enter a GSV/SSV instruction, the
programming software displays the valid object classes, object names, and
attribute names for each instruction. Restrictions exist for using the GSV and
SSV instructions with safety components.
For more information on which safety attributes are accessible via GSV and SSV
instructions, refer to the following:
•
GuardLogix Controllers User Manual, publication
•
1768 Compact GuardLogix Controllers User Manual,
publication
For general information on using GSV and SSV instructions, refer to the
Logix5000 Controllers General Instructions Reference Manual, publication
IMPORTANT
The safety task cannot perform GSV or SSV operations on standard
attributes.
The attributes of safety objects that can be written by the standard task are
for diagnostic purposes only. They do not affect safety task execution.
Содержание 1756-L61S ControlLogix 5561S
Страница 10: ...10 Rockwell Automation Publication 1756 RM093J EN P April 2018 Preface Notes...
Страница 64: ...64 Rockwell Automation Publication 1756 RM093J EN P April 2018 Chapter 6 Safety Application Development Notes...
Страница 70: ...70 Rockwell Automation Publication 1756 RM093J EN P April 2018 Chapter 7 Monitor Status and Handle Faults Notes...
Страница 114: ...114 Rockwell Automation Publication 1756 RM093J EN P April 2018 Index Notes...
Страница 115: ......