Rockwell Automation Publication 1756-RM001I-EN-P - May 2012
37
ControlLogix Communication Modules
Chapter 4
Use two 1756-EN2TR EtherNet/IP modules for SIL 2 safety loops. Each
redundant input must be routed through separate EtherNet/IP communication
modules.The SIL 2 output and its secondary shutoff must be routed through the
separate 1756-EN2TR EtherNet/IP modules.
DeviceNet Scanner Module
The 1756-DNB scanner module connects the controller to devices on a
DeviceNet network. You can use the 1756-DNB module to communicate only
nonsafety data to devices outside of the safety loop.
Data Highway Plus - Remote
I/O Module (1756-DHRIO)
The 1756-DHRIO module supports both Data Highway Plus and the
Remote I/O network of communication. You can use the 1756-DHRIO module
to communicate only nonsafety data to devices outside of the safety loop. For
example it may be used to communicate alarms to the Distributed Control
System (DCS).
SynchLink Module
The SynchLink module (catalog number 1756-SYNCH) is used for CST time
propagation between multiple chassis for event recording. The module can be
used only outside of the safety loop. It must not be used for any safety-related
activity in a SIL 2-certified ControlLogix system.
General Requirements for
Communication Networks
Follow these requirements when using SIL 2-certified communication modules:
•
When installing ControlLogix communication modules, carefully follow
the information provided in the module’s installation instructions.
•
DH+ can be used for communication to Human-to-Machine Interfaces
(HMI) and for communicating with the nonsafety portion of the system.
For more information on using HMI, see
,
Human-to-Machine Interfaces on page 91
.
•
For controllers that are not part of the SIL 2 safety function, use
listen-only connections to monitor SIL 2 I/O modules.
•
You must not use the Quick Connect feature when using a Ethernet
communication for SIL 2 safety I/O.
•
Non-SIL 2 devices should not write data to SIL 2 controllers. The only
exception to this is the use of HMI devices. For more information on how
to use HMI in the safety loop, see
Human-to-Machine Interfaces on page 91
.
Содержание 1756-L6 Series
Страница 24: ...24 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 1 SIL Policy Notes ...
Страница 60: ...60 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 5 ControlLogix I O Modules Notes ...
Страница 76: ...76 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 6 FLEX I O Modules Notes ...
Страница 120: ...120 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix C PFD Calculations for a SIL 2 System Notes ...
Страница 126: ...126 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix D Checklists Notes ...
Страница 133: ...Allen Bradley Motors ...