Rockwell Automation Publication 1734-UM007E-EN-P - October 2015
Chapter 1
Install the Module
3.
Insert the module straight down into the mounting base.
4.
Press to secure. The module locks into place.
Install the Removable
Terminal Block
A removable terminal block (RTB) comes with your mounting base assembly. To
remove, pull up on the RTB handle. This lets you remove and replace the
mounting base as necessary without removing any of the wiring.
To reinsert the removable terminal block, proceed as follows.
1.
Insert the RTB end opposite the handle into the base unit. The end has a
curved section that engages with the mounting base.
2.
Rotate the terminal block into the mounting base until it locks itself in
place.
NODE:
1734
SSI
WARNING:
When you connect or disconnect the removable terminal block
(RTB) with field-side power applied, an electrical arc can occur. This could cause
an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Hook the RTB end in to the
mounting base end, and rotate
until it locks into place.