Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
Install POINTBlock I/O Modules
79
Output Wiring Diagram
Outputs are electronically protected to 0.75 A. Module outputs are selectable for
latched mode or auto-reset mode. (Latched/auto reset is set by module, not by
individual channel.) Each channel is assigned a bit in the data table to indicate the
faulted condition. Outputs in the latched mode can only be reset with a user
command to the module.
ATTENTION:
When connecting more than one wire in a
termination point, make sure that both wires are the same gauge
and type.
Channel
Output Terminal
Common Terminal
Power
Remote Termination Block 3
Channel 0
0
6
Channel 1
1
7
Channel 2
2
4
Channel 3
3
5
Remote Termination Block 4
Channel 4
0
6
Channel 5
1
7
Channel 6
2
4
Channel 7
3
5
Module power is supplied from the internal power bus.
ATTENTION:
When connecting more than one wire in a
termination point, make sure that both wires are the same gauge
and type.
Out 0 Out 1
Out 3
Out 2
C
C
C
C
Load
Load
Load
Load
V = 12/24V dc, C = Common
Field power is supplied from internal power bus
0
2
6
3
1
7
4
5
Содержание 1734-OB2
Страница 4: ...Publication 1734 UM001E EN P July 2013 iv Summary of Changes Notes...
Страница 16: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 xxiv Notes...
Страница 22: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 6 About the Modules Notes...
Страница 116: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 118 POINT I O Module Data Notes...
Страница 156: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 158 Troubleshoot with the Indicators Notes...
Страница 168: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 176 Default Data Maps Notes...
Страница 172: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 180 Mounting Dimensions Notes...