Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
POINT I/O Module Data
103
Data
The1734-IE2C module operates in unipolar mode only; the 1734-IE2V module
operates in unipolar or bipolar modes. Data returned from the module is scaled
by the user to any 16-bit signed integer (–32,768…+32,767). Six bytes of data are
read from the 1734-IE2C and 1734-IE2V modules. No data is written to the
input modules.
•
Channel 0 Data (2 bytes)
•
Channel 1 Data (2 bytes)
•
Channel 0 Status (1 byte)
•
Channel 1 Status (1 byte)
Communicate with Your Module
I/O messages are sent to (consumed) and received from (produced) the
POINT I/O modules. These messages are mapped into the processor’s
memory.
(1)
These POINT I/O input modules produces six bytes of input data
(scanner Rx) and fault status data. It does not consume output data (scanner Tx).
(1) These are mapped through scan lists in DeviceNet networks and Direct, Listen Only, or Rack-optimized
connections in ControlNet and EtherNet/IP networks.
Default Data Map for the 1734-IE2C Analog Input Module
Message Size: 6 Bytes
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Produces (scanner Rx)
Input Channel 0 High Byte
Input Channel 0 Low Byte
Input Channel 1 High Byte
Input Channel 1 Low Byte
Status Byte for Channel 1
Status Byte for Channel 0
OR
UR
HHA LLA
HA
LA
CM
CF
OR
UR
HHA
LLA
HA
LA
CM
CF
Consumes (scanner Tx)
No consumed data
Where:
CF = Channel Fault status; 0 = no error, 1 = fault
LA = Low Alarm; 0 = no error, 1 = fault
LLA = Low/Low Alarm: 0 = no error, 1 = fault
UR = Underrange; 0 = no error, 1 = fault
CM = Calibration Mode; 0 = normal, 1 = calibration mode
HA = High Alarm; 0 = no error, 1 = fault
HHA = High/High Alarm; 0 = no error, 1 = fault
OR = Overrange; 0 = no error, 1 = fault
Default Data Map for the 1734-IE2V Analog Input Module
Message Size: 6 Bytes
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Содержание 1734-OB2
Страница 4: ...Publication 1734 UM001E EN P July 2013 iv Summary of Changes Notes...
Страница 16: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 xxiv Notes...
Страница 22: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 6 About the Modules Notes...
Страница 116: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 118 POINT I O Module Data Notes...
Страница 156: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 158 Troubleshoot with the Indicators Notes...
Страница 168: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 176 Default Data Maps Notes...
Страница 172: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 180 Mounting Dimensions Notes...